1MRK 505 370-UUS Rev. K
QCBAY also provides blocking functions that can be distributed to different apparatuses within the bay.
There are two different blocking alternatives:
•
Blocking of update of positions
•
Blocking of commands
IEC13000016 V2 EN-US
Figure 142: APC - Local remote function block
12.3.4
Switch controller SCSWI
SCSWI may handle and operate on one three-phase device or three one-phase switching devices.
After the selection of an apparatus and before the execution, the switch controller performs the following
checks and actions:
•
A request initiates to reserve other bays to prevent simultaneous operation.
•
Actual position inputs for interlocking information are read and evaluated if the operation is
permitted.
•
The synchronism check/synchronizing conditions are read and checked, and performs operation
upon positive response.
•
The blocking conditions are evaluated
•
The position indications are evaluated according to given command and its requested direction
(open or closed).
The command sequence is supervised regarding the time between:
Busbar protection REB670
Application manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC13000016-2-en.vsd
Section 12
Control
M16596-3 v7
305