1MRK 505 370-UUS Rev. K
QCBAY also provides blocking functions that can be distributed to different apparatuses within the bay.
There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
IEC13000016 V2 EN-US
Figure 142: APC - Local remote function block
12.3.4
Switch controller SCSWI
SCSWI may handle and operate on one three-phase device or three one-phase switching devices.
After the selection of an apparatus and before the execution, the switch controller performs the following
checks and actions:
A request initiates to reserve other bays to prevent simultaneous operation.
Actual position inputs for interlocking information are read and evaluated if the operation is
permitted.
The synchronism check/synchronizing conditions are read and checked, and performs operation
upon positive response.
The blocking conditions are evaluated
The position indications are evaluated according to given command and its requested direction
(open or closed).
The command sequence is supervised regarding the time between:
Busbar protection REB670
Application manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC13000016-2-en.vsd
Section 12
Control
M16596-3 v7
305