ABB Relion 670 series Engineering Manual
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

Quick Links

®
Relion
670 SERIES
670 series
Version 2.2 IEC
Engineering manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 series

  • Page 1 ® Relion 670 SERIES 670 series Version 2.2 IEC Engineering manual...
  • Page 3 Document ID: 1MRK 511 398-UEN Issued: May 2019 Revision: E Product version: 2.2 © Copyright 2017 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The...
  • Page 7: Table Of Contents

    Protection and control engineering .............. 57 Creating an application configuration with ACT............... 57 6.1.1 Overview............................57 6.1.2 Function blocks..........................59 6.1.3 Signals and signal management....................60 6.1.4 Conditional blocking functionality...................61 6.1.5 Function block execution parameters..................61 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 8 Cut-Paste and Copy-Paste of ACT GOOSE variables............110 8.4.6 GOOSE Online Monitoring .......................110 Engineering of vertical and horizontal communication in IET600........110 Importing SCL files to PCM600....................112 8.6.1 Importing SCD files........................112 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 9 Creating Template......................... 134 11.7.1 Creating a Mapping Template....................134 11.7.2 Applying Mapping Template on IED..................134 11.7.3 Exporting FPN templates......................135 11.8 Reporting and Printing........................135 Section 12 Glossary......................137 12.1 Glossary............................137 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 11: Introduction

    IEDs. The installation and commissioning personnel must have a basic knowledge of handling electronic equipment. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 12: Product Documentation

    The manual provides instructions for the monitoring, controlling and setting of the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 13: Document Revision History

    Documents related to REB670 Document numbers Application manual 1MRK 505 370-UEN Commissioning manual 1MRK 505 372-UEN Product guide 1MRK 505 373-BEN Technical manual 1MRK 505 371-UEN Type test certificate 1MRK 505 373-TEN 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 14 Documents related to RES670 Document numbers Application manual 1MRK 511 407-UEN Commissioning manual 1MRK 511 409-UEN Product guide 1MRK 511 410-BEN Technical manual 1MRK 511 408-UEN Type test certificate 1MRK 511 410-TEN 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 15: Document Symbols And Conventions

    The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 16: Document Conventions

    Edition 1 logical nodes Edition 2 logical nodes AEGPVOC AEGGAPC AEGPVOC AGSAL AGSAL AGSAL SECLLN0 ALMCALH ALMCALH ALMCALH ALTIM ALTIM ALTMS ALTMS ALTRK ALTRK BCZPDIF BCZPDIF BCZPDIF Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 17 BICPTRC BICPTRC BRCPTOC BRCPTOC BRCPTOC BRPTOC BRPTOC BRPTOC BTIGAPC B16IFCVI BTIGAPC BUSPTRC_B1 BUSPTRC BUSPTRC BBSPLLN0 BUSPTRC_B2 BUSPTRC BUSPTRC BUSPTRC_B3 BUSPTRC BUSPTRC BUSPTRC_B4 BUSPTRC BUSPTRC Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 18 BZNPDIF_Z3 BZNPDIF BZNPDIF BZNPDIF_Z4 BZNPDIF BZNPDIF BZNPDIF_Z5 BZNPDIF BZNPDIF BZNPDIF_Z6 BZNPDIF BZNPDIF BZNSPDIF_A BZNSPDIF BZASGAPC BZASPDIF BZNSGAPC BZNSPDIF BZNSPDIF_B BZNSPDIF BZBSGAPC BZBSPDIF BZNSGAPC BZNSPDIF Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 19 EF2RDIR GEN2PHAR GEN2PHAR PH1PTOC PH1PTOC EF4PTOC EF4LLN0 EF4PTRC EF4PTRC EF4RDIR EF4RDIR GEN4PHAR GEN4PHAR PH1PTOC PH1PTOC EFPIOC EFPIOC EFPIOC EFRWPIOC EFRWPIOC EFRWPIOC ETPMMTR ETPMMTR ETPMMTR Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 20 LCPTTR LCPTTR LCPTTR LCZSPTOC LCZSPTOC LCZSPTOC LCZSPTOV LCZSPTOV LCZSPTOV LD0LLN0 LLN0 LDLPSCH LDLPDIF LDLPSCH LDRGFC STSGGIO LDRGFC LEXPDIS LEXPDIS LEXPDIS LEXPTRC LFPTTR LFPTTR LFPTTR Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 21 PHPIOC PSLPSCH ZMRPSL PSLPSCH PSPPPAM PSPPPAM PSPPPAM PSPPTRC QCBAY QCBAY BAY/LLN0 QCRSV QCRSV QCRSV RCHLCCH RCHLCCH RCHLCCH REFPDIF REFPDIF REFPDIF ROTIPHIZ ROTIPHIZ ROTIPHIZ ROTIPTRC Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 22 T2WPTRC T3WPDIF T3WPDIF T3WGAPC T3WPDIF T3WPHAR T3WPTRC TCLYLTC TCLYLTC TCLYLTC TCSLTC TCMYLTC TCMYLTC TCMYLTC TEIGAPC TEIGGIO TEIGAPC TEIGGIO TEILGAPC TEILGGIO TEILGAPC TMAGAPC TMAGGIO TMAGAPC Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 23 ZMFPDIS ZMFPDIS ZMFPTRC ZMFPTRC ZMMMXU ZMMMXU ZMHPDIS ZMHPDIS ZMHPDIS ZMMAPDIS ZMMAPDIS ZMMAPDIS ZMMPDIS ZMMPDIS ZMMPDIS ZMQAPDIS ZMQAPDIS ZMQAPDIS ZMQPDIS ZMQPDIS ZMQPDIS ZMRAPDIS ZMRAPDIS ZMRAPDIS Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 24 LPTTR LPTTR LPTTR MVGAPC MVGGIO MVGAPC O2RWPTOV GEN2LLN0 O2RWPTOV O2RWPTOV PH1PTRC PH1PTRC PHPIOC PHPIOC PHPIOC QCBAY QCBAY BAY/LLN0 QCRSV QCRSV QCRSV RCHLCCH RCHLCCH RCHLCCH Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 25 U2RWPTUV VMMXU VMMXU VMMXU VMSQI VMSQI VMSQI VNMMXU VNMMXU VNMMXU VSGAPC VSGGIO VSGAPC WRNCALH WRNCALH WRNCALH XENCPOW XENCPOW ZCPSCH ZCPSCH ZCPSCH ZCRWPSCH ZCRWPSCH ZCRWPSCH Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 26 1MRK 511 398-UEN E Introduction Function block name Edition 1 logical nodes Edition 2 logical nodes ZCVPSOF ZCVPSOF ZCVPSOF ZGTPDIS ZGTLLN0 ZGPDIS ZGPDIS ZGPTRC ZGPTRC ZRWPDIS PSRWPDIS ZRWPDIS ZRWPTRC 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 27: Engineering Tool Set

    The Ethernet connection can then later also be used for service and maintenance purposes. The connection is also used to handle disturbance records in COMTRADE format from IEDs using the IEC 61850 file transfer or FTP. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 28: Ied Engineering Process

    IET600 or with the PCM600 built in IEC 61850 configuration tool. PCM600 interacts with IET600 by importing and exporting SCL files. The built in tool can be used for small projects including ABB IEDs only. To engineer communication between ABB IED's and third party devices it's recommended to use IET600.
  • Page 29 Configuration of the central account server, deployment and management of IED certificates. See the Cyber security deployment guideline for more information. • Defining allowed activities for the user profiles to use the read and write function. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 30 The connection between the IED and PCM600 is established via an Ethernet link on the front or rear port on the IED. The IP addresses of the different ports on the IED are not allowed to belong to the same subnet. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 31: Engineering Process

    This means that several iterations may be needed to finish the project. • Setting up the PCM600 project • Build the plant structure according to the substation structure. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 32 • Use the IET600 station configuration tool or the PCM600 IEC 61850 Configuration tool for IEC 61850 engineering. • See the application manual for other protocols (LON, SPA, IEC103). 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 33: Setting Up A Project

    IED type in PCM600. Procedure Close PCM600 before running the IED connectivity package installation. Install the IED series Connectivity package base. Select and install the IED modules as required. Install the documentation. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 34: Setting Technical Key

    Error message due to mismatch between PCM600 and IED technical key Be sure that the IED object in PCM600 has the same IP address as the physical IED, which is intended to be connected. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 35 A dialog window opens to inform about the technical key concept. OK in the dialog window. Click The technical key is read from the IED and the technical key editor window opens, see Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 36: Setting Up Communication Between Pcm600 And The Ied

    A link via a station LAN or from remote via a network. The physical connection and the IP address must be configured in both cases to enable communication. The communication procedures are the same in both cases. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 37 Ethernet interfaces together without a hub, router, bridge or switch in between. If an IED is equipped with optical LC interface, a converter between RJ-45 and LC is needed. Select Search programs and files in the Start menu in Windows. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 38 1MRK 511 398-UEN E Setting up a project IEC13000057-1-en.vsd IEC13000057 V1 EN-US Figure 8: Select: Search programs and files Type View network connections and click on the View network connections icon. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 39 IEC13000059-1-en.vsd IEC13000059 V1 EN-US Figure 10: Right-click Local Area Connection and select Properties Select the TCP/IPv4 protocol from the list of configured components using this connection and click Properties. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 40 IEC13000062-1-en.vsd IEC13000062 V1 EN-US Figure 12: Select: Use the following IP address ping command to verify connectivity with the IED. Use the Close all open windows and start PCM600. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 41: Project Managing In Pcm600

    Projects on my computer . Open Click the icon New Project . To create new project currently open projects and object tools shall be closed. New Project window opens, see Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 42: Building A Plant Structure

    Project = project name Substation = name of the substation Voltage Level = voltage level in substation Bay = bay within the voltage level IED = IED in the bay. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 43: Iec 61850 Naming Conventions To Identify An Ied

    PCM600 takes care of these two possibilities. The two possible signal designations are available per object in the object properties for all hierarchical levels beginning with the station as the highest level. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 44 The IED has been renamed as "SB1" The renamed full path name of the technical key for the IED would be DMSTATC1Q1SB1. GUID-BDE605BB-5ACA-456A-9334-65B3CE3C46F5 V2 EN-US Figure 15: PCM600: IEC 61850 signal designation concept 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 45: Changing The Scl Version Of An Ied

    This is useful when an order-specific IED is used. The order configuration is written to the IED at the factory, and can be accessed by PCM600. The housing type, the 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 46 Import a pre-configured IED available as a *.pcmt file. Inserting an IED in online mode An IEC 61850 edition 2 mode cannot be inserted in an IEC 61850 edition 1 project and vice versa. Procedure: 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 47 It is also possible to drag an IED from the Object Types window to the Bay level. Online Configuration mode, see Select the Figure IEC09000711-2-en.vsd IEC09000711 V2 EN-US Figure 18: PCM600: Configuration mode selection wizard Select the IED Communication protocol, see Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 48 The user cannot scan data from the IED or proceed further if the IED is not online or if the IP address is not correct. Scan option to scan/read the IED Type and IED Version for the IED that is online, Click the Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 49 Cancel the insertion or Figure 23. It is possible to Finish . confirm the configuration and do the insertion with IEC09000715-5-en.vdsx IEC09000715 V5 EN-US Figure 23: PCM600: IED Setup completion wizard 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 50 A template IED can only be inserted when the bay is selected in the plant structure. Procedure to insert a template IED Bay in the plant structure. Right-click the 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 51 IEC17000043 V1 EN-US Figure 24: Insert an IED from the template library New and Create from Template ... to open the Create New Object from Template Select window, see Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 52 Create New Object from It is possible to insert more than one IED from the Template window and the selection window remains open until the user Close . clicks 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 53 It is possible to give the inserted IED in the plant structure a user-defined name. Be sure to only user characters a-z, A-Z, 0-9 and _. Do not use space character in IED names. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 54: Setting Ied Ip Address In The Project

    IEC09000713 V2 EN-US Figure 27: Alternative 1: IP address via the first Wizard window Object Properties window, see • Via the IP address property of the IED in the Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 55 Open the IP address row and enter the IP address. Place the cursor on the The used alternative depends on the time at which the IP address is available. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 57: Ethernet Configuration Tool

    PTP VLAN tag is only valid for PTP time synchronization and it must have the same value in station clock and in the IED. The default value is set to 0. Columns in this tab will vary based on IED capability and order-specification. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 58 Enable/Disable IEC 61850 GOOSE communication on an access point. DNP 3.0 Enable/Disable DNP 3.0 protocol on an access point. Enable/Disable File Transfer Protocol on an access point. Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 59 Changing settings in this tab will not have any impact on the SCL model. The IED can be configured to receive IEC 61850–9–2E sample value streams from merging units. This tab’s availability will be based on order-specification. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 60 IEC16000191-1-en.vsdx IEC16000191 V1 EN-US Figure 31: Example of invalid configuration 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 61: Starting The Ethernet Configuration Tool

    GUID-3DB1C6C8-09C6-4460-A903-AA722888AFD9 v1 The tool can be started the from the IED level in the Plant Structure window in PCM600. Right click on the IED. Select Ethernet configuration from the menu. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 62 Section 5 1MRK 511 398-UEN E Ethernet configuration tool IEC16000094-1-en.vsdx IEC16000094 V1 EN-US 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 63: Protection And Control Engineering

    Some function blocks are mapped as logical nodes according to the IEC 61850 standard. Other function blocks are not mapped as logical nodes, for example: • Logical gates • Timers 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 64 SMT, they will not be shown in SMT. • Document the application configuration, for example to make printouts. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 65: Function Blocks

    Set visibility for execution order, cycle time and instance number. • Manage signals, for example hide, show and rearrange. • Invert Boolean inputs and Boolean outputs. Mandatory signals must be connected. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 66: Signals And Signal Management

    Boolean input and output signals may need to be inverted to fulfill the logic. ACT supports to add the inversion logic to a binary signal. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 67: Conditional Blocking Functionality

    GUID-ADA51480-0DE7-4D18-9B23-99EB3B5E8813 v8 Three function block execution parameters have influence on the runtime execution of the function block within the application configuration. Execution Order • • Cycle Time Instance Number • 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 68: Series Engineering Manual

    IED type, one or more possibilities may be available. The combination Execution Order , Instance Number is predefined by ABB. Mainly for basic AND , OR , a set of combinations spread over the full logic function blocks like for example range of execution orders is available.
  • Page 69: Configuration Parameters

    2. The following function blocks in group 3 must have a higher execution order than the main function block in group 2. 6.1.6 Configuration parameters GUID-52044790-0A7C-4D83-8634-887593A903BC v4 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 70: Connections And Variables

    That prevents for using a hardware binary output channel twice. As an example, see Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 71: Validation

    Example: If the user connects output from higher execution order function to inputs of lower execution order function. • Errors, marked by a red circle with a cross • Example: A mandatory input signal that is not connected. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 72: Setting Configuration And Setting Parameters In Pst

    To export parameters from PST, both XRIO and CSV formats are supported. All variables listed and shown in the parameter list can be sorted into two groups: • Configuration parameter or • Setting parameter 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 73: Graphical Parameter Setting Tool

    Underimpedance protection for generators and transformers ZGVPDIS Power swing detection ZMRPSB Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS Phase selection, quadrilateral characteristic with settable angle FRPSPDIS Faulty phase identification with load encroachment FMPSPDIS 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 74: Connecting Signals In Smt

    Glue logic means inserting a logical gate (OR and AND blocks) between the function blocks and the binary output channel. This can be engineered in SMT. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 75 It is possible to group and collapse hardware channels in SMT to get a better overview. Depending on the IED capability, SMT has a separate sheet for each possible combination. The possible sheets are: • Binary Inputs • Binary Outputs • GOOSE Receive 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 77: Local Hmi Engineering

    The operation mode of the function keys and LEDs is defined in the Parameter Setting tool. • The presented text labels on the LCD for LHMI keys and LEDs. • Graphical Display Editor with assistance of the Application Configuration tool, for example 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 78 LCD [A]. They are operated by keys [a] and [b]. The other group is the five function keys with their LEDs and the corresponding text elements on the LCD [B]. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 79 Only the programming of the signals is needed for the LEDs. • The operation mode of the LEDs is defined in the Parameter Setting tool. Function block FNKEYMD1 to 5 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 80 Each LED can illuminate in one of three colors: RED, YELLOW, GREEN. • Only one color is illuminated at a time. • The priority for illumination and the color is linked. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 81 • The timers are set in the Parameter Setting tool in the function block LEDGEN. IEC09000657-1-en.vsd IEC09000657 V1 EN-US Figure 50: LHMI: LED operation mode 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 82: Led Operation Modes

    In the Follow-F mode, the LED starts flashing when receiving a steady binary other times it is unlit. SeeFigure 52. This mode may be used to indicate that a tap changer or Petersen coil is moving. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 83 (acknowledged or unacknowledged) of each color. Excluding presentation of a state of higher priority always overrides the presentation of any state of lower priority. Figure 54 Figure 55 for these two principles. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 84 The LED remains lit even if the signal immediately transitions to On . acknowledged, the LED is switched off, unless the attached signal remains SeeFigure 56 for details. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 85 Auto- Reset Man- Reset S1LED S2LED S3LED S4LED Illumination => = Steady = Flash IEC08000401.vsd IEC08000401 V1 EN-US Figure 58: LHMI LED operation mode LatchedReset-S / 2 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 86: Single-Line Diagram Engineering

    It is important to link correctly between the HMI display page and the corresponding bay that is presented as a single line diagram on this HMI page. Rules to handle HMI pages: 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 87 The standard (IEC or ANSI) for the symbols and the selection of the font size for the text elements can be changed using the icons and drop down on top of the page window. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 88 Click to start and move the mouse pointer to the destination connection point. Center once again the mouse pointer and click to drop the line. Draw all line elements that are necessary. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 89: Supported Single-Line Diagram Symbols

    Definitions Connections Junction Connections Busbar junction Connections Feeder end Connections Earth Connections Star point Measuring Current transformer transformers Measuring Voltage transf. 2 windings transformers Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 90 LT6CPDIF L6CPDIF LT3CPDIF L3CPDIF TCLYLTC BZNSPDIF BZNTPDIF Others Capacitor Others Surge arrestor Others Reactor Others Motor Others Generator Others Coil Others Fuse Others Resistor Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 91 Isolator motor-operated, 11 = Undefined Switchgear Breaker, 00 = Middle position SCSWI, VSGAPC Breaker, 01 = Open Breaker, 10 = Closed Breaker, 11 = Undefined Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 92 Isolator2 indication only, 11 = Undefined Switchgear Breaker2, 00 = Middle position SCSWI, VSGAPC Breaker2, 01 = Open Breaker2, 10 = Closed Breaker2, 11 = Undefined Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 93 VSGAPC Texts Select button, 00 = Middle position VSGAPC Select button, 01 = Open Select button, 10 = Closed Select button, 11 = Undefined Table continues on next page 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 94: Bay Configuration Engineering

    11. Save the complete picture. 12. Repeat the steps for all pages when more than one is needed. 13. Write the display configuration to IED from the GDE tool. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 95 Select Input Signal . A list of the Right-click the measurement symbol and select engineered measurement application function blocks opens. Select the measurement application function block that corresponds to the selected symbol. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 96 Factor in the object properties (see Figure 65) to display values in more readable units (for example MW). Be sure to write the proper unit under the Unit Text field. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 97: Events And Indications

    To get IED events to the LHMI event list and indications for LEDs, disturbance report needs to be engineered. Detailed information about disturbance report subfunctions is found in the technical manual. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 99: Iec 61850 Communication Engineering

    When configuring RER670 for 9-2LE streams in a 16.7Hz system, the IED shall be set to 16.7Hz and the MU to 50Hz (4kHz sampling). 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 100: Iec 61850 Interface In Ied

    The upper part is the visible function block in ACTApplication Configuration tool and the lower part is the logical node data for the function block. Horizontal data communication between IEDs is illustrated in Figure 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 101: Goose Data Exchange

    In the opposite direction the standard only defines the IED as a receiver of the GOOSE message. How the GOOSE input signals are handled must be defined in the IED application 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 102: Station Configuration Description File Types

    Description of the substation part including the used logical nodes • Description of the IEDs with their logical nodes • Description of the communication network • Description of the engineering process 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 103: Exporting Scl Files From Pcm600

    Operation must be set to On . setting 8.3.1 Exporting SCD files GUID-2FDA859B-3761-4310-BEFF-11BB046A406B v3 Procedure for exporting SCD files from PCM600: Select the sub-station in the plant structure (see Figure 71). 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 104: Exporting Icd Or Cid Files

    Figure 73): • Configured IED Description (*.cid) for the IEC 61850 structure as needed for the IED at runtime. • IED Capability Description (*.icd) for the IEC 61850 structure. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 105: Easy Goose Engineering In The Application Configuration Tool

    GOOSE engineering does not replace GOOSE engineering in the Signal Matrix Tool (SMT) or the IEC 61850 Engineering tool. Easy GOOSE Engineering is supported for both IEC 61850 Edition 1 and IEC 61850 Edition 2 configured IEDs. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 106: User Interface

    The Sender IEDs list displays all selected sender IEDs compatible data attributes that can be received for the selected receiving signal. • Application Configuration: Application configuration tab displays all selected sender IEDs data attributes for signals that are visible in Application Configuration. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 107 Figure 76: Application configuration tab in Connect to GOOSE dialog window • SCL Configuration: SCL Configuration tab displays all selected sender IEDs IEC 61850 data attributes for signals that are not visible in Application Configuration. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 108 "Connect to GOOSE dialog window user interface – Extended Mode". Select GOOSE Block and Signal dialog window This dialog window will provide a list of compatible GOOSE Receive function blocks and corresponding GOOSE input signals. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 109 Function block name and signal name are considered as filtering. Extended mode In the “Connect to GOOSE” dialog window, Extended Mode is selected to create multiple GOOSE connections directly without selecting an input signal in the Application Configuration. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 110: Enable Easy Goose Engineering In Pcm600

    Enable Easy GOOSE Engineering in PCM600 GUID-65A0F83C-522C-4920-AA2D-479A640ECE28 v1 Select Tools/Options In Options/Application Configuration, open the “Configuration” tab Under the “GOOSE configuration” section, check “Allow configuring GOOSE in Application Configuration”. Click “OK” to exit. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 111: Making Goose Connections In The Application Configuration Tool

    Create GOOSE connections via GOOSE receive functions GUID-F16104FF-C8BB-4455-807E-336E1AA09124 v1 Select and right click on the input signal of the GOOSE Receive function, point to “Connect” and select the “GOOSE” option. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 112 SCL configuration tab (see Figure 77). Click on the “Connect” button. For more information on SCL configuration data attributes, see Section "User interface". In this case, the GOOSE connection will be added as shown in Figure below. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 113: Create Goose Connections Via Normal Function Blocks

    For more information on the GOOSE Receive blocks, see Section "User interface" Click on the “Connect” button, the GOOSE connection will be added to the configuration as shown in Figure below. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 114: Connect To Goose Dialog Window User Interface - Extended Mode

    Under “Receiver IED” section, select GOOSE Receive or normal function input signal. Under “Sender IEDs” section, select and right click on data attribute in either Application Configuration or SCL Configuration tab Click on Connect option. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 115: Connecting To A Iec 61850 Scl Data Attribute From Sending Ied

    Signal matrix tool, the GOOSE configuration is also added to the application configuration in the sender IED and the receiver IED as shown in Figure 82, 83, 85, and 86. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 116: Deleting Connections

    IET600 GUID-04ED1306-BAE6-49D2-8C84-11849EACC711 v9 For IEC 61850 engineering, a separate system configuration tool may be needed with PCM600 (for example, when using other than ABB IEDs). Procedure for vertical engineering using IET600: Create a project in IET600. Import the SCD file exported from PCM600.
  • Page 117 MinTime and MaxTime , and update as required. for GOOSE control block, for eaxample Connect the GOOSE control block to receiving IEDs that subscribe GOOSE data. Export the SCD file. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 118: Importing Scl Files To Pcm600

    In SMT, configure connections between signals the server is sending and the GOOSE receive function blocks. If a client is defined for GOOSE receive, at least one cross in SMT is required to write the configuration to the IED. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 119: Importing Icd Or Cid Files

    IED. This is done through a full Write to IED... from the context menu or the Tools menu. During the write process, the user is asked to update the communication configuration: 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 120 IED. Click No in the Update Communication window to keep the existing communication configuration in the IED. IEC09000729-2-en.vsd IEC09000729 V2 EN-US Figure 90: Update communication configuration window in PCM600 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 121: Iec 60870-5-103 Communication Engineering

    “OPTICAL103:1” for the optical serial channel on the SLM • “RS485103:1” for the RS485 port The protocol to activate on a physical port is selected under: Main menu/Configuration/Communication/Station Communication/Port configuration/ • RS485 port 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 122 GI data from being delivered after a new spontaneous event, the pending GI event is modified to contain the same value as the spontaneous event. As a result, the GI dataset is not time-correlated. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 123: Section 10 Dnp3 Communication Engineering

    Configure ACTVGRP (Basic IED functions) and SP16GAPC (Monitoring) with the Application Configuration Tool (ACT). 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 124 Signal Type to Binary Input Open the Communication Management Tool (CMT). Set the Object , and choose the connection of the master for which the values should be presented. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 125: Configuring Dnp3 Protocol Signals

    Figure 94: Selecting the signals into the DNP signal list 10.3 Configuring DNP3 protocol signals GUID-4908ED38-733F-4A8B-AEB2-90C0CB9A5274 v4 Save the actual project configuration in PCM600 to make all signals visible for CMT. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 126 The left window has a drop down menu for signal selection and buttons for signal movement, see Figure IEC09000722-2-en.vsd IEC09000722 V2 EN-US Figure 97: CMT: Container window design when selecting DNP3 protocol Procedure to move signals: Select one or several signals. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 127: Setting Dnp3 Signal Parameters

    Click the two inner arrows to sort signals to another index sequence, or select from the context menu to move one or a set of signals to another array, see Figure 100. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 128: Configuring Dnp3 Class

    Unsolicited reporting is possible as well. Modify the organization of the classes for each signal individually. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 129 None and 0 to 3 according to the project Select the signal classes and choose between demands. OK to set the signal classification. Click Write to IED. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 131: Section 11 Flexible Product Naming

    The IEC 61850 structure mapping displays customer data structure and customer data attribute on the left; internal data structure and internal data attribute on the right. Object Properties 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 132: Ied And Signal Naming Convention

    Right click on a substation level. Select and click Import from the Menu. IEC17000022-1-en.vsdx IEC17000022 V1 EN-US Figure 105: Importing SCD file Browse and select the SCD file. Click Open to open the file. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 133: Starting The Iec 61850 Structure Mapping Tool

    The FPN object’s name is displayed in the column on the left and the name of the mapped PCM600 internal object is displayed in the column on the right. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 134: Iec 61850 Structure Mapping

    The tool will display all FPN IEDs and all PCM600 IEDs in separate lists. Mapping will be done by dragging and dropping the PCM600 IED on the right hand side to FPN IED on the left hand side. The tool indicates the mapping status visually. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 135 Data tree view consists of Customer Data Structure in the column on the left and the name of the mapped PCM600 Internal Data Structure in the column on the right. IEC17000025-1-en.vsdx IEC17000025 V1 EN-US Figure 110: Data tree view 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 136: Data Attribute Mapping

    The mapping status is indicated visually. It can be seen what FPN data attribute is mapped to what PCM600 internal data attribute and how many FPN data attributes are mapped to a PCM600 internal data attribute. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 137: Data Attribute Level Mapping

    Drag a data object from the customer data structure onto a data object in the internal data structure • Drag a data object from the internal data structure onto a data object in the customer data structure. 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 138: Logical Node Level Mapping

    It is possible to exclude all unmapped data attributes from the mapping at once by right-clicking and selecting the exclude all option. IEC17000033-1-en.vsdx IEC17000033 V1 EN-US Figure 116: Excluding data attributes from mapping 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 139: Setting The Data Attribute Value

    Once the FPN mapping is complete, all mapping can be validated in three ways using the validate option available in quick access menu Validate All Validate Current Validate Selected IEC17000029-1-en.vsdx IEC17000029 V1 EN-US Figure 118: Validate mapping 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 140: Creating Template

    The template can be applied either in the IEC 61850 structure mapping tool or in the PCM600 plant structure. In the IEC 61850 structure mapping tool, the template can be applied to one or 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 141: Exporting Fpn Templates

    Table 8: Data Attribute Mappings Customer Data Attribute Internal Data Attribute Signal Name Application/ CTRULLN0.Beh.stVal [ST] LLN0.Mod.origin.orCat [ST] CB111.LN0.Mod.stVal [ST] CTRULLN0.Beh.stVal [ST] CB 111.LN0.Mod . t [ST] CTRULLN0.Beh.t [ST] 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 143: Section 12 Glossary

    United Nations-sponsored standards body within the International Telecommunications Union. CAN carrier module CCVT Capacitive Coupled Voltage Transformer Class C Protection Current Transformer class as per IEEE/ ANSI CMPPS Combined megapulses per second 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 144 DRAM Dynamic random access memory Disturbance report handler Digital signal processor Direct transfer trip scheme Ethernet configuration tool EHV network Extra high voltage network Electronic Industries Association Electromagnetic compatibility 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 145 HSAR High speed autoreclosing High-availability Seamless Redundancy High-voltage HVDC High-voltage direct current Installation and Commissioning Tool for injection based protection in REG670 IDBS Integrating deadband supervision International Electrical Committee 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 146 Local area network LIB 520 High-voltage software module Liquid crystal display LDCM Line data communication module Local detection device Light-emitting diode LON network tool Local operating network Miniature circuit breaker 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 147 RMS value Root mean square value RS422 A balanced serial interface for the transmission of digital data in point- to-point connections RS485 Serial link according to EIA standard RS485 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 148 US Department of Defense protocol suite based upon these, including Telnet, FTP, UDP and RDP. Time delayed earth-fault protection function Transport Layer Security Transmit (disturbance data) 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 149 Three times zero-sequence current.Often referred to as the residual or the earth-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage 670 series Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 152 ABB AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website www.abb.com/protection-control © Copyright 2017 ABB. All rights reserved.

This manual is also suitable for:

Version 2.2 iec

Table of Contents