OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative nominal value for
analog input M in percent of nominal value.
14.6.4.4
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of that particular input,
will be fetched and shown in the disturbance summary on local HMI. If not set (Hide), status change will
not be indicated.
SetLEDN: Set red LED on local HMI in front of the IED if binary input N changes status.
Disturbance recorder
OperationM: Analog channel M is to be recorded by the disturbance recorder (Enabled) or not (Disabled).
If OperationM = Disabled, no waveform (samples) will be recorded and reported in graph. However, Trip
value, pre-fault and fault value will be recorded and reported. The input channel can still be used to trig
the disturbance recorder.
If OperationM = Enabled, waveform (samples) will also be recorded and reported in graph.
Setting information
SetInfoInDrep: Parameter used to enable or disable the settings information in disturbance header.
Event recorder
Event recorder (ER) function has no dedicated parameters.
Trip value recorder
ZeroAngleRef: The parameter defines which analog signal that will be used as phase angle reference for
all other analog input signals. This signal will also be used for frequency measurement and the measured
frequency is used when calculating trip values. It is suggested to point out a sampled voltage input
signal, for example, a line or busbar phase voltage (channel 1-30).
Sequential of events
function has no dedicated parameters.
14.6.4.5
Consideration
The density of recording equipment in power systems is increasing, since the number of modern IEDs,
where recorders are included, is increasing. This leads to a vast number of recordings at every single
disturbance and a lot of information has to be handled if the recording functions do not have proper
settings. The goal is to optimize the settings in each IED to be able to capture just valuable disturbances
and to maximize the number that is possible to save in the IED.
The recording time should not be longer than necessary (PostFaultrecT and TimeLimit).
Should the function record faults only for the protected object or cover more?
How long is the longest expected fault clearing time?
Is it necessary to include reclosure in the recording or should a persistent fault generate a second
recording (PostRetrig)?
Minimize the number of recordings:
Busbar protection REB670
Application manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 14
Monitoring
M12179-389 v3
M12179-448 v4
M12179-446 v5
GUID-B0D40F6D-3CE4-4FF3-81B4-B453FDD389CB v1
M12179-444 v4
M12179-442 v3
M12179-440 v3
M12179-420 v6
397

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reb670

Table of Contents