Web Server - JUMO LOGOSCREEN 601 Operating Manual

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

9.5

Web server

The integrated web server provides the user with convenient access to process values, various visual-
izations, and the device's alarm and event list from a web browser. Access can be password protected.
The device has a maximum of 2 MB memory for HTML pages. The start page, index.htm, is available by
default; access with the web browser is performed by entering the device's IP address. If needed, you
can also use the DNS device name.
NOTE!
The Microsoft Silverlight
er displays a note and offers to install it.
Supported web browser: Microsoft Internet Explorer
Setup dialog box
Online visualization
The online visualization is configurable as a standard version or user version.
In the Standard version a distinction is made between a standard device and an FDA device (extra code
888):
Standard device (version: standard): all functions are available.
FDA device (version: 21 CFR Part 11): the "Import" and "Delete" functions are locked; the FDA com-
pliant web application that is created by the manufacturer is always transferred to the device. Only
data is displayed in the web browser; entering comments is not possible.
The User version does not include a default web application. Creation and use of the web application
are the customer's responsibility. All functions are available.
1
Microsoft, Silverlight, and Internet Explorer are registered trademarks of the Microsoft Corporation.
9 Configuration – in setup program only
1
plug-in is required for this function. If the plug-in is not present, the web brows-
1
215