Modbus Slave - JUMO LOGOSCREEN 601 Operating Manual

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

7 Configuration
Parameter
Data format
Min response
time
Line break char-
acter
(setup only)
7.22.1

Modbus slave

The device acts as a Modbus slave.
Device dialog box
Parameter
Parameter
Device address
?
Timeout
monitoring
?
182
Selection/settings
Data format with which the interface is operated.
8 - 1 - no parity
8 - 1 - odd parity
8 - 1 - even parity
0 to 40 to 500 ms
$
Blank space
.
;
:
-
Selection/settings
1 ... 254
No
Yes
Description
8 data bits, 1 stop bit, no parity
8 data bits, 1 stop bit, odd parity
8 data bits, 1 stop bit, even parity
The minimum response time is adhered
to by the Modbus slave before a re-
sponse is sent following a data request.
After receiving a response, the Modbus
master waits during this period before
sending a new request.
This character triggers a line break when
scanning batch texts (only for protocol =
barcode).
Description
Modbus device address
Monitoring is not active.
Monitoring is active.