Parameter
Switching differ-
ential
?
Alarm suppres-
sion
?
Alarm delay
?
Activation/type, limit value, switching differential
(1)
Limit value for min. alarm
(2)
Limit value for max. alarm
(3)
Switching differential
Alarm/Event list
All events and their time of occurrence are added to the event list. If the event is an alarm, newly occur-
ring alarms and their time of occurrence are additionally added to the alarm list. If an alarm is made in-
active, it is removed from the alarm list and the time of removal is added to the event list.
Alarm suppression, alarm delay
Alarm delay and alarm suppression delay or prevent entries being added to the event list and alarm list,
activation of the collective alarm, and display in the status bar.
Alarm delay
During an out-of-limit case, the status signal is only activated after the delay time has expired. If the limit
value infringement no longer exists at that point, the time for the next limit value infringement restarts
from zero.
Selection/settings
0 to 99999
Digital selector
No selection
0 s to 32767 s
(3)
(1)
7 Configuration
Description
The switching differential is used to sup-
press constant switching of the status
signal in the event of fluctuations of the
input signal around the limit value.
The selected digital signal (high-active)
prevents the status signal being activat-
ed.
Delay time for status signal activation
(3)
(2)
1
Status signal on
0
Status signal off
1
0