Analog Inputs - JUMO LOGOSCREEN 601 Operating Manual

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

7 Configuration
7.5

Analog inputs

The analog inputs (optional extra) are universal analog inputs for connecting various measuring probes.
For example, the analog inputs are pooled into groups together with other analog signals via the
"Groups" configuration and are available for further use via these groups.
Device dialog (excerpt)
Parameter
Parameter
Channel designa-
tion
Channel descrip-
tion
Sensor
104
Selection/settings
AI ...
Use default text or enter other text.
Analog input ...
Use default text or enter other text.
Selection of measuring probe for the relevant analog input
Inactive
RTD temp. probe 2-w
RTD temp. probe 3-w
RTD temp. probe 4-w
Resistance/potentiometer 2-w
Resistance/potentiometer 3-w
Resistance/potentiometer 4-w
Resistance transmitter
Thermocouple
Voltage 0 to 70 mV
Description
Name (abbreviation) with max. 5 charac-
ters that is used in the visualizations.
Description (designation) with max. 21
characters (e.g. for curve diagram)
No sensor selected
Deviating default setting for analog input
1 to 3 (see below)
RTD temperature probe in two-wire cir-
cuit
RTD temperature probe in three-wire cir-
cuit
RTD temperature probe in four-wire cir-
cuit
Resistor/potentiometer in two-wire circuit
Resistor/potentiometer in three-wire cir-
cuit
Resistor/potentiometer in four-wire cir-
cuit
Resistance transmitter
Thermocouple
Voltage signal