JUMO LOGOSCREEN 601 Operating Manual page 105

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

Parameter
Selection/settings
Voltage 0 to 1 V
Voltage -1 to +1 V
Voltage 0 to 10 V
Voltage -10 to +10 V
Current 0 to 20 mA
Current 4 to 20 mA
Temperature in-
In the case of a voltage/current signal, resistance/potentiometer, or resistance
put
transmitter, the measured value must be defined as a temperature to convert auto-
matically when changing the temperature unit.
No
Yes
Unit
Measured value unit for voltage/current signal, resistance/potentiometer or resis-
tance transmitter
%
(Max. 5 characters)
Linearization
Available options and default settings depend on the measuring sensor selected.
?
Linear
Pt50
Pt100
Pt500
Pt1000
Pt100 JIS
Pt50 GOST
Pt100 GOST
Cu50 GOST
Cu100 GOST
Ni100
Ni100 GOST
Fe-CuNi L
Fe-CuNi J
Cu_CuNi U
Cu-CuNi T
NiCr-Ni K
NiCr-CuNi E
NiCrSI-NiSi N
Pt10Rh-Pt S
Pt13Rh-Pt R
Pt30Rh-Pt6Rh B
W5Re-W26Re C
W3Re-W25Re D
W5Re-W20Re A1
Chromel®-Copel® L
Chromel®-Alumel®
Platinel II
7 Configuration
Description
Voltage signal
Voltage signal
Voltage signal
Voltage signal
Current signal
Default setting for analog input 1 to 3
Current signal
Measured value is not a temperature.
Measured value is a temperature.
The unit is displayed if the measured val-
ue is displayed in numerical form
IEC 751: 2008
IEC 751: 2008
IEC 751: 2008
IEC 751: 2008
JIS 1604
GOST 6651-2009 A.2
GOST 6651-2009 A.2
GOST 6651-2009 A.3
GOST 6651-2009 A.3
DIN 43760:1987-09
GOST 6651-2009 A.5
DIN 43710:1985-12
DIN EN 60584-1:2014
DIN 43710:1985-12
DIN EN 60584-1:2014
DIN EN 60584-1:2014
DIN EN 60584-1:2014
DIN EN 60584-1:2014
DIN EN 60584-1:2014
DIN EN 60584-1:2014
DIN EN 60584-1:2014
ASTM E230M-11
ASTM E1751M-09
GOST R 8.585-2001
GOST R 8.585-2001
GOST R 8.585-2001