JUMO LOGOSCREEN 601 Operating Manual page 225

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

Parameter
Alarm active at
Alarm/Event text
Alarm delay
?
Alarm suppression
?
Alarm/Event list
All events and their time of occurrence are added to the event list. If the event is an alarm, newly occur-
ring alarms and their time of occurrence are additionally added to the alarm list. If an alarm is made in-
active, it is removed from the alarm list and the time of removal is added to the event list.
Alarm delay
In the event of an alarm (parameter "Alarm active at"), the alarm signal is not activated until the delay
time has expired. If the alarm case is left in the meantime, the timer restarts when a new alarm case
occurs.
Alarm delay, alarm suppression
Alarm delay and alarm suppression delay or prevent entries being added to the event list and alarm list,
activation of the collective alarm, and display in the status bar.
ST editor
Press the corresponding button to start the ST editor.
There is a separate manual for the ST editor available with further information.
chapter 1.6.2 "Device documentation in the form of PDF files", Page 15
9 Configuration – in setup program only
Selection/settings
High (1)
Low (0)
Use default text or enter
other text.
0 s to 999 s
Digital selector
No selection
Description
Alarm at high level (1)
Alarm at low level (0)
Text entered in the alarm and event list and dis-
played in the status bar.
Delay time for activation of the alarm signal
The selected digital signal (high-active) prevents
the alarm signal being activated.
225

Advertisement

Table of Contents
loading

This manual is also suitable for:

706521

Table of Contents