JUMO LOGOSCREEN 700
Highly-Scalable Paperless Recorder
Brief Instructions
70653000T97Z001K000
V2.00/EN/00710320

Advertisement

Table of Contents
loading

Summary of Contents for JUMO LOGOSCREEN 700

  • Page 1 JUMO LOGOSCREEN 700 Highly-Scalable Paperless Recorder Brief Instructions 70653000T97Z001K000 V2.00/EN/00710320...
  • Page 3: Table Of Contents

    Contents Contents Introduction ........... . 7 Safety information .
  • Page 4 Contents 4.4.4 Digital inputs/outputs............32 4.4.5 Relays .
  • Page 5 Contents 6.1.6 Interfaces ..............80 6.1.7 Screen.
  • Page 6 Contents...
  • Page 7: Introduction

    Introduction 1 Introduction Safety information General This manual contains information that must be observed in the interest of your own safety and to avoid material damage. This information is supported by symbols which are used in this manual as indicated. Please read this manual before starting up the device.
  • Page 8: Intended Use

    1 Introduction Intended use The device is designed for use in an industrial environment as specified in the technical data. Other uses beyond those defined are not viewed as intended uses. The device has been manufactured in compliance with applicable standards and directives as well as the applicable safety regulations.
  • Page 9: Disposal

    1 Introduction The accompanying letter for repair (Supplementary sheet for product returns) can be downloaded online from the manufacturer's website: http://productreturn.jumo.info Protection against electrostatic discharge (ESD) (ESD = electrostatic discharge) To prevent damage due to ESD, electronic modules or components must be handled, packaged, and stored in an ESD-protected environment.
  • Page 10: Identifying The Device Version

    1 Introduction Identifying the device version 1.5.1 Nameplate The nameplate is affixed to the housing. Contents The nameplate contains important information. This includes: Description Designation on the Example nameplate Device type 706530/18-1124-25/260 Part no. 00123456 Fabrication number F-Nr. 0070033801219110006 Voltage supply AC/DC 20 to 30 V, 48 to 63 Hz Device type (Typ) Compare the specifications on the nameplate with the order.
  • Page 11: Order Details

    1 Introduction 1.5.2 Order details Basic type 706530 Paperless recorder with the following interfaces: 1x Ethernet, 2x USB (1x host, 1x de- vice), 1x RS232/485 interface, as well as a relay (changeover contact) Basic type extension Without software package With software package (setup program incl. USB cable, PC Evaluation Software PCA3000, PCA Communication Software PCC;...
  • Page 12: Scope Of Delivery

    Not used Universal carrying case, compact Subsequent expansion is only possible in JUMO Central Services. Analog inputs with increased electric strength (AC 300 V). For the calibration certificate it is necessary to state the channels along with the thermocouple type and the desired measuring points.
  • Page 13: Content Of The Technical Documentation

    1 Introduction Content of the technical documentation The documentation for this device is addressed to plant manufacturers and users with appropriate tech- nical expertise; it consists of the following documents. 1.6.1 Device documentation in printed form 70653000T97... Quick start guide (brief instructions) A hard copy of the quick start guide is part of the scope of delivery of the device.
  • Page 14: Documentation For Optional Software

    1 Introduction 70653000T97... Quick start guide (brief instructions) The quick start guide is also available as a PDF file and has the same scope as the printed document. 1.6.3 Documentation for optional software The following manuals in the form of PDF files are available for download from the manufacturer's web- site.
  • Page 15: Description

    Multiple versions of the JUMO LOGOSCREEN 700 are available for process data recording. The high level of scalability allows for flexible adaptation to various customer requirements: from the device ver-...
  • Page 16: Display And Control Elements

    2 Description Display and control elements (1) Touchscreen (TFT color screen) Technical data: chapter 6.1.7 "Screen", page 81 The screen appearance is described in the "Operation" chapter: chapter 5.1.1 "Touchscreen", page 37 (2) Alarm LED The LED is lit while an alarm is present. (3) Power LED The LED flashes after switching on the device until the startup process is completed.
  • Page 17: Mounting

    Mounting 3 Mounting General information on mounting WARNING! The device is not designed for use in potentially explosive areas. Explosion hazard.  Only deploy the device outside of potentially explosive areas. Mounting site The device is designed for installation in a panel cut-out. The front of the device and housing have dif- ferent protection types (see technical data).
  • Page 18: Dimensions

    3 Mounting Dimensions Device 120.9 Panel cut-out Close mounting Distance between panel cut-outs Horizontal Vertical Minimum clearance 20 mm 20 mm Recommended distance (easier mounting of mounting elements) 50 mm 50 mm Device with terminal cover (accessories) 128.1 147.6...
  • Page 19: Panel Mounting

    3 Mounting Panel mounting Step Action Insert the device into the panel cut-out from the front until the seal is flush with the panel. Insert the mounting elements into the recesses of the housing (one element on each cor- ner, see figure) and use a screwdriver to evenly clamp them against the rear side of the panel with a torque of 1.0 Nm.
  • Page 20: Terminal Cover (Accessories)

    3 Mounting CAUTION! Sharp or hard objects are not suitable for operating the screen. They can cause scratches and damage the front foil.  Only operate the screen with your finger or with a suitable stylus. Terminal cover (accessories) Step Action Screw the spacer bolt (A) into the rear wall of the device.
  • Page 21: Universal Carrying Case, Compact (Extra Code 970)

    3 Mounting Universal carrying case, compact (extra code 970) Dimensions Intended use The paperless recorder in the carrying case is intended only for use by personnel with technical qualifi- cations who have been specially trained, and have the relevant knowledge in the field of automation technology.
  • Page 22 3 Mounting chapter 6.1.10 "Case", page 82...
  • Page 23: Electrical Connection

    Electrical connection 4 Electrical connection Installation notes Requirements for personnel • Work on the device must only be carried out to the extent described and, like the electrical connec- tion, only by qualified personnel. • Before plugging and unplugging connecting cables, it must be ensured that the acting person is elec- trostatically discharged (by touching grounded metallic parts, for example).
  • Page 24: Galvanic Isolation

    4 Electrical connection Galvanic isolation Analog input 1 Analog output 1 Analog input 3 Analog output Analog output Analog input 10 3510 V Analog input Relay 1 Analog input 3510 V Analog input Relay 2 Analog input 3510 V Analog input Relay 7 Analog...
  • Page 25: Connection Elements

    4 Electrical connection Connection elements Front USB host interface (without cover) Back connection elements This graphic shows an exam- ple with specific options. Slot 4 (option 4) Slot 3 (option 3) Slot 2 (option 2) Slot 1 (option 1) Connection element and assignment Connection element and assignment USB device interface Relay 1 (changeover contact)
  • Page 26 4 Electrical connection NOTE! The front-side USB host interface is intended only for connecting a USB flash drive. Any other use is not admissible. NOTE! The quality of the USB cable and the USB flash drive affects whether or not the device functions correct- ly.
  • Page 27: Connection Diagram

    4 Electrical connection Connection diagram 4.4.1 Analog inputs Measuring probe Terminals and connection symbol Connection element.terminal / assignment Thermocouple Analog/digital option (order code 1) analog(HI)/digital option (order code 2): RTD temperature probe 7.1-5 / Analog input 1 8.1-5 / Analog input 2 Two-wire circuit 9.1-5 / Analog input 3 13.1-5 / Analog input 4...
  • Page 28 4 Electrical connection Measuring probe Terminals and connection symbol Connection element.terminal / assignment Resistance/potentiometer Analog option (order code 3): Three-wire circuit 6.1-5 / Analog input 10 7.1-5 / Analog input 11 8.1-5 / Analog input 12 Resistance/potentiometer 9.1-5 / Analog input 1 10.1-5 / Analog input 2 Four-wire circuit 11.1-5 / Analog input 3...
  • Page 29: Digital Inputs

    4 Electrical connection 4.4.2 Digital inputs Version Terminals and connection symbol Connection element.terminal / assignment Digital input DC 0/24 V, Analog/digital option 1 2 3 4 5 6 7 8 9 10 auxiliary voltage supply DC 24 V (order code 1): 6.1 / Digital input 1 6.2 / Digital input 2 Example: potential-free contact on...
  • Page 30 4 Electrical connection Version Terminals and connection symbol Connection element.terminal / assignment Digital input DC 0/24 V, Analog(HI)/digital option 1 2 3 4 5 6 7 8 9 10 auxiliary voltage supply DC 24 V (order code 2): 6.1 / Digital input 1 6.2 / Digital input 2 Example: potential-free contact on 6.3 / Digital input 3...
  • Page 31: Analog Outputs

    4 Electrical connection 4.4.3 Analog outputs Version Terminals and connection symbol Connection element.terminal / assignment Analog output Analog/digital option 1 2 3 4 5 6 7 8 DC 0 to 10 V or (order code 1): DC 0(4) to 20 mA 6.9 / Analog output 1 + (configurable) 6.10 / Analog output 1 -...
  • Page 32: Digital Inputs/Outputs

    4 Electrical connection 4.4.4 Digital inputs/outputs Version Terminals and connection symbol Connection element.terminal / assignment Digital input DC 0/24 V Digital option 1 2 3 4 5 6 7 8 (order code 4): digital output DC 0/24 V 24.1 / Digital input/output 1 (individually switchable), 24.2 / Digital input/output 2 Example: potential-free contact on...
  • Page 33 4 Electrical connection Version Terminals and connection symbol Connection element.terminal / assignment Digital input DC 0/24 V Analog(HI)/digital option 1 2 3 4 5 6 7 8 9 10 (order code 2): digital output DC 0/24 V 6.5 / Digital input/output 13 (individually switchable), 6.6 / Digital input/output 14 Example: potential-free contact on...
  • Page 34: Relays

    4 Electrical connection 4.4.5 Relays Version Terminals and connection symbol Connection element.terminal / assignment Relay (changeover contact) As a standard feature: (max. 3 A at AC 230 V, resistive load) Relay 1: 4.1 / Normally open contact (NO) 4.2 / Common contact (C) 4.3 / Normally closed contact (NC) Relay option (order code 5):...
  • Page 35: Rs232/Rs485 Interface

    4 Electrical connection 4.4.6 RS232/RS485 interface Version Connection element.pin / assign- Connection element ment RS232 3.2 / RxD (received data) 9-pin SUB-D socket 3.3 / TxD (transmission data) (switchable to RS485) 3.5 / GND (ground) RS485 3.3 / TxD+/RxD+ (transmission/re- 9-pin SUB-D socket ceived data +) (switchable to RS232)
  • Page 36 4 Electrical connection...
  • Page 37: Operation

    Operation 5 Operation Operating concept The device is equipped with a resistive touchscreen; the operation is menu-driven. User management protects the device against unauthorized access. The different users can be assigned different privileges so that they can only access specific functions. In addition to the visualizations available per default, the setup program can be used to create individual process screens for presenting process data.
  • Page 38 5 Operation Position Meaning Symbol Left Data transfer via PCC software - Transfer active - Transfer not active No icon Center Batch recording - Recording active - Recording not active (or batch not configured) No icon Right Operating mode - Standard operation - Event operation - Time operation The area on the right shows the logon status as an icon and the time.
  • Page 39: Led Displays

    5 Operation The area on the right contains buttons (icons) for screen navigation: The "Home" button takes the user directly to a specific screen (configurable). Pressing the "Next" button (right arrow) selects the next screen on a specific level (e.g., toggle to the next active group).
  • Page 40: Main Menu

    5 Operation Main menu The main menu contains functions for configuring, parameterizing, and operating the device. View Menu items Scroll up Quit main menu Scroll box (current position within the menu); movable Scroll down 5.2.1 Logon This is the menu in which users log on and off, and change their passwords. The following IDs, names, and passwords are set by default: Users Name...
  • Page 41: Configuration

    5 Operation chapter 5.8 "Electronic signature", page 69 5.2.2 Configuration This menu contains functions for configuring the device. The functions are available both on the device and in the setup program (see the "Configuration" chapter in the operating manual). In addition to this, there are functions that can only be configured with the setup program (see the oper- ating manual, chapter "Configuration - only in setup program"...
  • Page 42: Service

    5 Operation 5.2.6 Service This menu contains various service functions. Default configuration You can store the current device configuration with this function. Similarly, a previously stored configuration can be loaded as the current configuration. 5.2.7 Calibrating the touchscreen This menu enables you to calibrate the touchscreen (position calibration). To do so, you need to tap the center of the crosshairs shown in the corners of the screen one after another.
  • Page 43: Alarm List

    5 Operation 5.3.1 Alarm list The alarm list shows all alarms that are present in their order of occurrence. If an alarm is no longer pres- ent, its entry is automatically removed from the alarm list. The alarm list is rebuilt after power on. Each alarm represents an event.
  • Page 44: Event List

    5 Operation 5.3.2 Event list The event list contains event entries in chronological order. A maximum of 150 entries are stored and displayed. When new entries are added, the oldest entries are deleted. The event list is kept after power off.
  • Page 45 5 Operation Event list in memory view If the alarm and event menu is called up from the memory view (history) (or from the curve presentation of a completed batch), the event list is opened directly. An additional button is available here which lets you mark the time of a specific event in the memory view with the cursor position.
  • Page 46: Visualization Menu (Display)

    5 Operation Visualization menu (display) In the visualization menu, the display type and group that should currently be displayed on the device are selected. Up to 6 analog channels and 6 digital channels of a group can be shown on one screen. View Menu items Scroll up...
  • Page 47: Curve Diagram

    5 Operation 5.4.1 Curve diagram In the curve diagram, the analog and digital signals configured for the relevant group are displayed as analog curves or digital traces. Digital traces and channel information can be hidden in the group con- figuration. The diagram type (horizontal, vertical) is selected individually for each group in the configuration.
  • Page 48 5 Operation Memory view (history) Move time for memory values forward Time of memory values (cursor position) (later memory values) Cursor (time of numeric memory values) Zoom factor Move time for memory values back (ear- Navigation bar lier memory values) Analog value at selected time Navigation bar Quit memory view...
  • Page 49 5 Operation Horizontal diagram In the horizontal diagram, the analog curves and digital traces run from right to left. The channel infor- mation is shown on the right edge of the screen; the icons for event and alarm at the top edge of the screen.
  • Page 50: Digital Diagram

    5 Operation 5.4.2 Digital diagram In the digital diagram, the digital signals configured for the relevant group are displayed as digital traces. The diagram type (horizontal, vertical) is selected individually for each group in the configuration. The following view shows the vertical diagram. Accordingly, the description also applies to the horizontal di- agram.
  • Page 51: Bar Graph

    5 Operation 5.4.3 Bar graph In the bar graph view, the analog signals configured for the relevant group are shown as bar graphs, and the digital signals – depending on their logical state – as colored areas or frames. The diagram type selected for the group (horizontal, vertical) is irrelevant for the bar graph view. The view is always as a column diagram (vertical) and not as a bar diagram (horizontal).
  • Page 52: Text Image

    5 Operation 5.4.4 Text image The text image shows the current values for the analog signals configured for the relevant group as num- bers. The digital signals – depending on their logical state – are shown as colored areas or frames. Group view Designation (pointer) and signal abbrevi- Digital signal with signal abbreviation...
  • Page 53 5 Operation Individual view Designation (pointer), signal abbrevia- Bar graph (column diagram) of the ana- tion (configurable), and signal designa- log signal tion (configurable) of the analog signal Current value of analog signal Digital signal with signal abbreviation (configurable) and designation (pointer) Back to group view Displays the logical state: Colored area = HIGH (B1, B3)
  • Page 54 5 Operation Individual view with alarms Last alarm to have occurred (here: from Limit value for max. alarm (configurable) analog input 03) Current value of analog signal with color Bar graph (column diagram) of analog change (alarm) signal with color change (alarm) Alarm text of analog input Limit value for min.
  • Page 55: Report

    5 Operation 5.4.5 Report A report shows the statistical information for the relevant group. A report contains the maximum, mini- mum, and average values of the analog signals during the recording time (the recording period is con- figurable). A distinction is made between the current (ongoing) report and the completed report. To create a report, it must be activated in the configuration for the relevant group.
  • Page 56 5 Operation Detailed view Designation (pointer) and signal abbrevi- Completed report ation (configurable) of analog signal; re- port type (configurable; here: external) Time at which the max. value (or min. Current (ongoing) report value) occurred Time stamp for current report: beginning Back to previous view of recording and current time Time stamp for completed report: begin-...
  • Page 57: Current Batch

    5 Operation 5.4.6 Current batch This function opens the report for the current batch recording. Batch recording can be started and stopped (depending on the configuration). The report layout is defined in the batch configuration. This is where the individual lines of the report are defined, and the text for the left column, and content of the right column, are specified (device: main menu >...
  • Page 58: Completed Batch

    5 Operation 5.4.7 Completed batch This function displays the report for the completed batch recording. Recorded data can be shown as a report and as a curve diagram. If necessary, the report can also display the data from current batch recording. View Open report (statistical information for Open curve presentation (analog curves...
  • Page 59 5 Operation Report for batch Designation (pointer) and signal abbrevi- Data (statistical information) for the com- ation (configurable) of the analog signal pleted batch recording Go to the next analog signal within the Data (statistical information) for the cur- group rent (ongoing) batch recording Back to the batch report view Go to next group...
  • Page 60: Process Screen

    5 Operation 5.4.8 Process screen This visualization shows the individual process screens. You can use the arrow keys in the navigation bar to change to the next process screen. Process screens can be created with the setup program and transferred to the device. For a process screen to be displayed, it must be activated (configuration parameters in the setup program;...
  • Page 61: Comment Text

    5 Operation Detailed view Designation (configurable) of the count- Limit value for max. alarm (configurable) er/integrator Specifications on current counter/inte- Bar graph view of the current counter/in- grator tegrator The type (configurable; here: external) Start and end of the display range are decides when the status is stored and configurable.
  • Page 62: Text Input Dialog

    5 Operation In the case of a device that has extra code 888 (FDA), the setting in question is performed using the PCS software. The approach when entering a comment with authentication basically corresponds to the one when ren- dering an electronic signature for a completed batch (only steps 2 to 4). Example of an electronic signature: chapter 5.8 "Electronic signature", page 69 Text input dialog...
  • Page 63 5 Operation Text input dialog Parameter (designation of the configura- Input box with current text tion parameter from the previous dialog) After changing to the text input dialog, the current text is fully selected. Tapping on the input box displays a cursor. Tap- ping and dragging the cursor lets you se- lect multiple characters.
  • Page 64 5 Operation Keyboard mappings Each of the 30 keys in the default keyboard layout can be mapped with up to 10 characters. The Shift key toggles between the first two characters. To select more characters, you need to hold down the rel- evant key for longer.
  • Page 65: Flash Manager

    5 Operation Flash manager The Flash Manager menu automatically opens when the device is in basic status and a USB flash drive (FAT16/FAT32 file system) is plugged into the front USB port. If the device is in a menu (main menu, alarm and event list, display), the Flash Manager is opened only after exiting the menu.
  • Page 66 5 Operation choose any starting time in the past. Using the additional parameter "Save counters/reports" it is pos- sible to save the current readings of the counters and integrators as well as the statistics (report) – even if they have not yet been completed – along with the recording data. •...
  • Page 67 5 Operation Saving the recording data of a certain time period In the following example the recording data of a week should be saved. Select time period Determined starting time (editable) The starting time is automatically determined by the device depending on the current date (here: August 04, 2016), the current time (here: 15:00:00), and the selected time period.
  • Page 68: Web Server

    5 Operation Web server The device includes a built-in web server which supports online visualization with the help of a web browser. The user can access the process values, various visualizations, and the device's alarm and event list. For access, you need to enter the device's IP address in the address line of the web browser. If needed, you can also use the DNS device name.
  • Page 69: Electronic Signature

    5 Operation Electronic signature With the extra code 888 (FDA), the user has the option to provide a completed batch or the recording data of a certain time period with their electronic signature. A logged-on user can also provide their sig- nature during logoff –...
  • Page 70 5 Operation Step Action Select your user ID (in this case: master) The user has to select his/her ID. This step is required because someone other than the cur- rently logged-on user can provide this signature. Enter text that describes the meaning of the signature (evaluation text) using the keyboard. Alternatively, select text from the text list (1) and, if required, edit it: The possibilities of entering a text depend on the configuration (no text available, enter text via keyboard, select text from text list, select text from text list and edit).
  • Page 71 5 Operation Step Action Enter password: Confirm process: The process can still be aborted here.
  • Page 72 5 Operation Step Action In the report of the completed batch recording, press the button (1) to display the signature that was provided: The signature (here: master) and the meaning of the signature (here: batch o.k.) are dis- played:...
  • Page 73 5 Operation Time period The electronic signature for a time period essentially differs from the signature for the completed batch by requiring the time period in question to be selected. The signature applies to the time period that is displayed in the diagram at the time of the signature. The displayed period may have to be expanded prior to signing.
  • Page 74 5 Operation...
  • Page 75: Annex

    Annex 6 Annex Technical data 6.1.1 Analog inputs General Number Max. 18 (see connection diagram) A/D converter 24 bit delta-sigma Sampling rate Up to 18 channels: 125 ms Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s Galvanic isolation See "Galvanic isolation"...
  • Page 76 6 Annex RTD temperature probe Designation Standard Measuring range Accuracy Measur- ing cur- rent ≤ 0.1 % 500 μA Pt50 IEC 751:2008 ITS-90 -200 to +850 °C ≤ 0.1 % 500 μA Pt100 IEC 751:2008 ITS-90 -200 to +850 °C ≤...
  • Page 77 6 Annex Voltage, current (standard signals) Designation Measuring range Accuracy Input resistance or bur- den voltage ≤ 0.1 % > 500 kΩ Voltage 0 to 70 mV ≤ 0.05 % > 500 kΩ 0 to 10 V -10 to +10 V ≤...
  • Page 78: Digital Inputs

    6 Annex 6.1.2 Digital inputs Number Max. 18 (see connection diagram) Input Level Logic level 0: < 3.5 V; logic level 1: > 10 V Sampling rate 125 ms (max. counting frequency: 4 Hz) : < 1 kΩ; R : > 50 kΩ (use of auxiliary voltage 24 V) Potential-free contact High-speed input Usable inputs...
  • Page 79: Digital Inputs/Outputs

    6 Annex 6.1.4 Digital inputs/outputs Number Max. 24 (see connection diagram) Input or output Individually configurable as input or output Input Logic level 0: < 3.5 V; logic level 1: > 10 V Level Sampling rate 125 ms (max. counting frequency: 4 Hz) Potential-free contact : <...
  • Page 80: Interfaces

    6 Annex 6.1.6 Interfaces RS232/RS485 Number 1 (can be switched between RS232 and RS485) Connector type SUB-D 9-pin (socket) Baud rate 9600, 19200, 38400, 115200 Data format 8/1n, 8/1e, 8/1o Protocol Modbus RTU as master or slave; barcode scanner Application Communication with Modbus master/slave, connection of a barcode scanner External inputs Via Modbus master/slave functionality: 120 analog and 120 digital inputs, 64...
  • Page 81: Screen

    6 Annex 6.1.7 Screen Type TFT color screen/TFT-touchscreen (resistive) Size 14.5 cm (5.7") Resolution 640 × 480 pixels (VGA) Number of colors 65536 Frame rate 60 Hz (type) Brightness setting Adjustable on the device Screensaver (switch-off) After waiting period or due to control signal TFT color screens may have pixel errors due to technological and/or production-related reasons.
  • Page 82: Environmental Influences

    6 Annex Conductor cross section on termi- nals 6 to 23 Wire or stranded wire Min. 0.14 mm , max. 1.5 mm (with terminal cover: max. 0.5 mm without ferrule Stranded wire with ferrule Without plastic collar: min. 0.25 mm , max.
  • Page 83: Approvals And Approval Marks

    6 Annex 6.1.11 Approvals and approval marks Approval mark Testing facility Certificate/certification Inspection basis Valid for number c UL us Underwriters Submitted UL 61010-1 (3. Ed.), All versions of the built-in Laboratories CAN/CSA- device; not in conjunction 22.2 No. 61010-1 with extra code 970 (3rd Ed.) Buffer battery replacement...
  • Page 84: China Rohs

    6 Annex China RoHS 3URGXFW JURXS  &KLQD ((3 +D]DUGRXV 6XEVWDQFHV ,QIRUPDWLRQ &RPSRQHQW 1DPH +J &G &U 9, 3%'( +RXVLQJ *HKlXVH 3URFHVV FRQQHFWLRQ 3UR]HVVDQVFKOXVV 1XWV 0XWWHU 6FUHZ 6FKUDXEH ^: d 7KLV WDEOH LV SUHSDUHG LQ DFFRUGDQFH ZLWK WKH SURYLVLRQV 6-7  *%7  ,QGLFDWH WKH KD]DUGRXV VXEVWDQFHV LQ DOO KRPRJHQHRXV PDWHULDOV¶...
  • Page 85: Barcode

    6 Annex Barcode Initializing the barcode scanner The barcode scanner must be initialized once prior to use. Example: Step Action Scan the "Factory Default Settings" barcode. Scan the "Select RS-232 Standard" barcode. The relevant information and barcodes can be found in the manual for the barcode scanner being used. The paperless recorder supports the barcodes code 39 (standard variant) and code 128 (A and B, with- out control characters) as well as the QR code (without control characters).
  • Page 86 6 Annex Enter batch texts Step Action Scan the barcodes for the batch text of the individual lines one after the other (starting with the first line). All batch lines configured for the barcode input are populated with the scanned text one after the other (max.
  • Page 87 6 Annex Stop batch reporting Step Action Scan the STOP barcode. STOP Batch reporting is stopped. In the current batch report, and depending on the configuration of the batch line, texts loaded via barcode are either reset to the standard text (default text) (Configuration > Batch > Batch line: Delete line = Yes) or retained (Delete line = No).
  • Page 88: Texts And Process Values

    6 Annex 6.4.2 Texts and process values Specific control characters can be used to load event texts, process values (external text variables, an- alog and digital variables), or comment texts (batch recipes). Once the respective text has been scanned using the control character, the system automatically switch- es back to barcode input for batch control.
  • Page 89 6 Annex Enter binary value in external digital variable: %Bn% = enter as binary value into external digital variable n (n = number of variable) Example: %B1%1 %B 1 %1 The binary value 1 is entered into external digital variable 1. The entered value is available in the digital selector.
  • Page 90 6 Annex...
  • Page 92 JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc. Street address: JUMO House 6733 Myers Road Moritz-Juchheim-Straße 1 Temple Bank, Riverway East Syracuse, NY 13057, USA 36039 Fulda, Germany Harlow, Essex, CM20 2DY, UK Delivery address:...