JUMO LOGOSCREEN 601 Operating Manual page 171

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

Parameter
Annual
Total
Periodically
Period
Report by control
signal
?
Control signal
Synchronization
time
?
Out of range
?
Report by control signal
NOTE!
Within 5 seconds, only one external report is started in a group, i.e., any new external starts prior to the
5 seconds elapsing are ignored. If the start signal is still on after 5 seconds, the external report is started
immediately. If the start signal is no longer on, the report is not restarted.
Synchronization time
The synchronization time parameter will be explained in more detail below, using the example of a peri-
odical report. The stop and restart are performed at the next point in time occurring in the time grid –
depending on the synchronization time and period.
Example:
Period = 2 hours
Synchronizat. time = 11:30:00
Power on = 09:11:00
1st period from 09:11 to 09:30 = 19 minutes
2nd period from 09:30 to 11:30 = 2 hours
3rd period from 11:30 to 13:30 = 2 hours
Selection/settings
Specifies whether a report runs for a whole year. Completion and restart occur at
00:00 on the first day of the year
Off, On
Total specifies whether a report is to be run for the total duration of the current con-
figuration of the device.
Off, On
Specifies whether a periodic report runs. Completion and restart are determined by
the period and synchronization time parameters.
Off, On
1 min to 12 h
Specifies whether an external report runs while the control signal is active.
Off, On
Digital selector
No selection
Synchronizat. time is used as the report end and restart for the daily, weekly, and
periodical report.
00:00:00
This parameter decides what happens if an analog channel is outside of the valid
measuring range (scaling).
Stop report
Delete report
7 Configuration
Description
If "On", the yearly report will be run.
If "On", the total report will be run.
If "On", the periodical report runs.
Period is used as the report end and re-
start for the periodical report.
If "On", the external report will be run.
Control signal (high active) for the exter-
nal report
Time of synchronization
The reports for this channel are stopped.
If the measured values are within the
measuring range limits, these will be re-
started.
The reports are set to invalid ("-----") and
only restarted following the configured
report end.
171