7 Configuration
Parameter
Response in case
of a fault
?
Replacement val-
ue
Scaling start, scaling end
A value range is assigned to the physical output signal by specifying the zero point and end value (scal-
ing). The default setting corresponds to a value range of 0 to 100%.
If, for example, a temperature with a value range from 150 °C to 500 °C is to be issued via an analog
output with signal type 0 to 20 mA, the start value must be set to 150 (corresponding to 0 mA) and the
end value to 500 (corresponding to 20 mA).
Response in case of a fault
Output value in the event of fault:
Signal type (parameter "Output signal")
Voltage 0 to 10 V
Current 0 to 20 mA
Current 4 to 20 mA
Voltage 10 to 0 V
Current 20 to 0 mA
Current 20 to 4 mA
This behavior also applies for probe/wire break or probe/conductor short-circuit. Error detection depends
on the type of measuring probe (see technical data, measuring circuit monitoring).
chapter 11.1.1 "Analog inputs", Page 265
Limits according to NAMUR recommendation NE 43 for signal type 4 to 20 mA:
Measurement information M
Failure information A
for deviation below measured value/short-circuit ("NAMUR Low")
Failure information A
for deviation above measured value/probe break ("NAMUR High")
112
Selection/settings
Value of the output signal after deviation above or below the measuring range (out
of range = o-o-r)
The selection options "Defined low value" and "Defined high value" are only avail-
able for the output signals 4 to 20 mA and 20 to 4 mA.
Replacement value
Defined low value
Defined high value
0 to 22 mA or
0 to 10 V
(depending on output signal)
Description
Configurable value (parameter "Re-
placement value")
Value for deviation below measured val-
ue/short-circuit according to NAMUR
recommendation
Value for deviation above measured val-
ue/probe break according to NAMUR
recommendation
Value of the output signal in the event of
deviation above or below the measuring
range
Output value
Replacement value (configurable)
Replacement value (configurable)
Replacement value (configurable) or
Defined low value (1 mA) or
Defined high value (22 mA)
Replacement value (configurable)
Replacement value (configurable)
Replacement value (configurable) or
Defined low value (1 mA) or
Defined high value (22 mA)
3.8 to 20.5 mA
≤ 3.6 mA
≥ 21 mA