JUMO LOGOSCREEN 601 Operating Manual page 115

Paperless recorder with touchscreen
Hide thumbs Also See for LOGOSCREEN 601:
Table of Contents

Advertisement

Device dialog box
Parameter
Parameter
Activation
Alarm/Event list
?
Alarm active at
Alarm/Event text
Alarm delay
?
Alarm suppres-
sion
?
Alarm/Event list
All events and their time of occurrence are added to the event list. If the event is an alarm, newly occur-
ring alarms and their time of occurrence are additionally added to the alarm list. If an alarm is made in-
active, it is removed from the alarm list and the time of removal is added to the event list.
Selection/settings
Inactive
Active
Inactive (signal only)
Event
Alarm/event
High (1)
Low (0)
Use default text or enter other text.
0 s to 32767 s
Digital selector
No selection
7 Configuration
Description
Signal monitoring is inactive.
Signal monitoring is active.
In the event of an alarm, only the alarm
signal is activated.
The alarm/event text is entered in the
event list.
The alarm/event text is entered in the
alarm list and the event list. The collec-
tive alarm is activated and the text of the
last alarm to occur is displayed in the sta-
tus bar.
Alarm at high level (1)
Alarm at low level (0)
Text entered in the alarm and event list
and displayed in the status bar.
Delay time for alarm signal activation
The selected digital signal (high-active)
prevents the alarm signal being activat-
ed.
115