A.2 Accessories
Figure A-10
A.2.3
MOBY I migration
The RF300 readers of the 2nd generation provide the option of simple migration of existing
MOBY I systems to SIMATIC RF300. The so-called MOBY I emulation processes frames of the
MOBY I protocol on its serial interface and communicates with the established RF300
transponders.
If the RF300 reader is connected to a communication module with MOBY I capability, the reader
automatically recognizes the serial protocol and sets the MOBY I protocol. As a communication
module with MOBY I capability, all the communication modules sold for MOBY I count regardless
of the mode in which the MOBY I communication modules are operated. This property allows
even projects with the ECC mode turned on or with file handlers to be migrated.
Communication modules with MOBY I capability:
RF180C, RFID 181EIP, RF170C, ASM 456, ASM 475, ASM 470, ASM450, ASM 451, ASM 452, ASM
472, ASM 473, ASM 424, ASM 454, ASM 400, CM 422, CM 423, ASM 410, ASM 420, ASM 421,
ASM 440, ES030
With the aid of the adapter cable (0.3 m; article number 6GT2091-4VE30) you can migrate
existing MOBY I projects without needing to re-cable the connected RFID devices.
The transfer is as usual with MOBY I with a transmission speed of 19.2 kBd. The transmission
speed in the application is identical (or slightly slower) than with the original MOBY I hardware.
NOTICE
Changed field geometry
When replacing MOBY I components with RF300 components note that the field geometry
changes.
454
Dimension drawing of fixing hood 6GT2690-0AE00
System Manual, 02/2021, C79000-G8976-C345-09
SIMATIC RF300