5.4 SIMATIC RF360R
Accessories required
You need the following accessories:
• For connecting the power supply
M12 plug (4-pin, L-coded) and 4-wire cable (4 x 1.5 mm
• for PROFINET IO connection
M12 plug (4-pin, D-coded) and 4-wire Ethernet cable (Twisted Pair, shielded)
You can find the associated article numbers in the section "Ordering data (Page 462)".
Connect the plug
Proceed as follows to connect the device:
1. Push the respective plug into the corresponding round socket on the reader.
Make sure the connectors and sockets are properly interlocked (tongue and groove).
2. Fasten the connector by tightening the knurled locking ring.
To guarantee the degree of protection, you must fasten all connectors with ≃ 1.0 Nm.
178
NOTICE
Ensuring the degree of protection
You need to close all unused sockets with M12 sealing caps to ensure IP65 or IP67 degree
of protection. You can find the order data of the sealing caps in the section "Ordering data
(Page 462)".
NOTICE
Using only one PROFINET interface
If only one PROFINET interface is required, it is essential to use the outer socket "X1 P2R" for
reasons of interference immunity.
Close the unused socket "X1 P1R" with a sealing cap.
)
2
System Manual, 02/2021, C79000-G8976-C345-09
SIMATIC RF300