This document contains information for installation, commissioning, operation and maintenance staff. It is intended to support device installation and commissioning. Reference documents: Manual (Operation and setting) AUMATIC AC 01.2 Parallel Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (refer to <Addresses>). Table of contents Page Safety instructions.........................
Page 3
Indications..........................7.1. Indications during commissioning 7.2. Indications in the display 7.2.1. Feedback indications from actuator and valve 7.2.2. Status indications according to AUMA classification 7.2.3. Status indications according to NAMUR recommendation 7.3. Mechanical position indicator/running indication 7.4. Indication lights Signals.............................
Page 4
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Table of contents AC 01.2 Non-Intrusive 11.2. Maintenance 11.3. Disposal and recycling Technical data......................... 12.1. Features and functions of actuator 12.2. Features and functions of actuator controls 12.3. Service conditions 12.4.
Any device modification requires prior consent of the manufacturer. 1.2. Range of application AUMA part-turn actuators are designed for the operation of industrial valves, e.g. butterfly valves and ball valves. Other applications require explicit (written) confirmation by the manufacturer. The following applications are not permitted, e.g.:...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Safety instructions AC 01.2 Non-Intrusive Escalators Continuous duty Buried service Permanent submersion (observe enclosure protection) Potentially explosive areas, with the exception of zone 22 Radiation exposed areas in nuclear power plants No liability can be assumed for inappropriate or unintended use.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Safety instructions Indicates a potentially hazardous situation with a low level of risk. Failure to observe this warning may result in minor or moderate injury. May also be used with property damage.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Identification AC 01.2 Non-Intrusive Identification 2.1. Name plate Each device component (actuator, controls, motor) is equipped with a name plate. Figure 1: Arrangement of name plates Actuator name plate Controls name plate Motor name plate Additional plate, e.g.
This commission number can be used to directly download the wiring diagram (in German and English language), inspection records and further information regarding the device from the Internet: http://www.auma.com. For some details, the customer number might be required. Actuator serial number...
Page 10
(push buttons and display) and perform settings (contents of these instructions). read in or out data or modify and save settings via the AUMA CDT software (option), using a computer (laptop or PC). The connection between computer and AUMATIC is wireless via Bluetooth interface (not included in these instruc- tions).
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Transport, storage and packaging Transport, storage and packaging 3.1. Transport For transport to place of installation, use sturdy packaging. Hovering load! Risk of death or serious injury. Do NOT stand below hovering load.
SQR 14.2 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Assembly 4.1. Mounting position AUMA actuators and actuator controls can be operated without restriction in any mounting position. 4.2. Handwheel fitting Information For transport purposes, handwheels from a diameter of 400 mm are supplied separ- ately.
Page 13
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Assembly Figure 6: Coupling fitting dimensions Coupling Valve shaft Grub screw Screw Table 2: Coupling fitting dimensions Type, size - output mounting flange X max [mm] Y max [mm] Z max [mm] SQ/SQR 05.2-F05...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Fasten actuator with screws [4]. Information: We recommend applying liquid thread sealing material to the screws to avoid contact corrosion. Fasten screws [4] crosswise with a torque according to table. Table 3: Tightening torques for screws Screws Tightening torque T...
Page 15
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Assembly Electrostatic discharge ESD! Risk of damage to electronic components. Earth both operators and devices. Loosen screws and remove the local controls. Check whether O-ring is in good condition, correctly insert O-ring. Turn local controls into new position and re-place.
The pertaining wiring diagram/terminal plan (in German and English language) is plan attached to the device in a weather-proof bag, together with these operation instructions. It can also be obtained from AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com). Permissible networks...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive 5.2.1. Terminal compartment: open Figure 10: Connection AUMA plug/socket connector, version S Cover Screws for cover O-ring Screws for socket carrier Socket carrier Cable entry...
Page 19
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Electrical connection Remove cable sheathing. Strip wires. For flexible cables: Use end sleeves according to DIN 46228. Connect cables according to order-related wiring diagram. In case of a fault: Hazardous voltage while protective earth conductor is NOT connected! Risk of electric shock.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive 5.2.3. Terminal compartment: close Figure 13: Example: Version S Cover Screws for cover O-ring Screws for socket carrier Socket carrier Cable entry Blanking plug Cable gland (not included in delivery) Short-circuit due to pinching of cables! Risk of electric shock and functional failures.
Observe prior to connec- tion We recommend: AUMA cable set LSW20. If the AUMA cable set is not used: Use suitable flexible and screened connecting cables. Use separate, CAN bus data cable for MWG of 120 Ohm character imped- ance (e.g. UNITRONIC BUS-FD P CAN UL/CSA - 2 x 2 x 0.5 mm², man- ufacturer: Lapp).
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Figure 15: Parking frame 5.3.3. Protection cover Protection cover for plug compartment when plug is removed. The open terminal compartment can be closed using a protective cover (not illustrated).
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation Operation Valve damage due to incorrect basic setting! Prior to electrical operation of the actuator, the basic settings i.e. type of seating, torque and limit switching have to be completed. 6.1.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Figure 18: Local controls Push button for operation command in direction OPEN Push button STOP Push button for operation command in direction CLOSE Push button RESET Selector switch Hot surfaces, e.g.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation The bottom row of the display [6] serves as navigation support and explains which push buttons [1 4] are used for menu navigation. Figure 19: [1 4] Push buttons or navigation support Selector switch Display...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Figure 21: Marking with ID ID starts with = status menu ID starts with = main menu It is possible to select between status menu S and main menu M: Group selection For this, set selector switch to 0 (OFF), hold down push button C for approx.
Default factory password: 0000 Service (5) Service staff Change configuration settings AUMA (6) AUMA administrator 6.4.1. Password entry Select desired menu and hold down push button for approx. 3 seconds. Display indicates the set user level, e.g Observer (1) Press Up ▲to select a higher user level and press...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Select parameter Change passwords either: Change passwords click via the menu to parameter, or via direct display: press and enter ID M0229 Display indicates: ▶ Change passwords The user level is indicated in the top row (1 6), e.g.: For user level 1 (view only), passwords cannot be changed.
Page 29
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation Enter password (→ enter password). Display indicates: ▶ Language and Save (bottom row) Language selection 10. Select new language via Up ▲ Down ▼ resulting in the following significa- tions: black triangle: ▶...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Indications 7.1. Indications during commissioning When switching on the power supply, all LEDs on the local controls illuminate for LED test approx. 1 second. This optical feedback indicates that the voltage supply is connected to the controls and all LEDs are operable.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications Figure 29: Information in the status bar (top) Operation mode Error symbol (only for faults and warnings) ID number: S = Status page If further details or information are available with reference to the display, the following Navigation support indications Details or More appear in the navigation support (bottom display row).
Page 32
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Torque (S0002) The indication is only available if the actuator is equipped with an MWG (magnetic limit and torque transmitter). S0002 on the display indicates the torque applied at the actuator output. The bargraph display appears after approx.
Page 33
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications If the positioner is enabled and activated, the bargraph indication for E1 (position Setpoint control setpoint) is displayed. The direction of the operation command is displayed by an arrow above the bargraph indication.
(P1, P2, ...) selected position (1, 2, ...) ) no position selected Actual position value 7.2.2. Status indications according to AUMA classification These indications are available, if the parameter Diagnostic classific. M0539 is set to AUMA. Warnings (S0005) If a warning has occurred, the display shows S0005: the number of warnings occurred a blinking question mark after approx.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications Figure 41: Fault For further information, please also refer to <Corrective action>. 7.2.3. Status indications according to NAMUR recommendation These indications are available, if the parameter Diagnostic classific. M0539 is set to NAMUR.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Figure 44: Maintenance required For further information, please also refer to <Corrective action>. Failure (S0011) The S0011 indication shows the causes of the failure indication according to NAMUR recommendation NE 107.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications 7.4. Indication lights Figure 47: Arrangement and signification of indication lights Marking with symbols (standard) Marking with figures 1 6 (option) End position CLOSED reached (blinking: for operation in direction CLOSE) 2 Tc Torque fault CLOSE Motor protection tripped 4 To Torque fault OPEN...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Signals AC 01.2 Non-Intrusive Signals 8.1. Status signals via output contacts (digital outputs) Output contacts are used to send status signals (e.g. reaching the end positions, Characteristics selector switch position, faults...) as binary signals to the control room. Status signals only have two states: active or inactive.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Figure 48: End stop Screw plug for end stop OPEN Setting screw for end stop OPEN Screw plug for end stop CLOSED Setting screw for end stop CLOSED Dimensions/sizes 05.2 07.2...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) If the valve end position is not reached: Slightly turn setting screw [2] counterclockwise until valve end position OPEN can be safely set. Turning the setting screw [2] clockwise results in a smaller swing angle.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Press Display indicates the current setting: Limit or Torque The bottom row of the display indicates either: Edit → continue with step 6 Save →...
Page 43
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Select parameter either: Select parameter click via the menu to parameter, or via direct display: press and enter ID M0088. Display indicates: Trip torque CLOSE Up ▲...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive 9.4. Limit switching: set Valve damage at valve/gearbox due to incorrect setting! When setting with motor operation: Stop actuator before reaching end of travel (press push button STOP).
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Re-set end position CLOSED: Set end position CLOSED CMD0009 9.1 For large strokes: Set selector switch in position Local control (LOCAL) and operate actuator in motor operation via push button (CLOSED) in direction of the end position.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive 9.5.1. Direction of rotation: check Move actuator manually to intermediate position or to sufficient distance from end position. Switch on actuator in direction CLOSE and observe the direction of rotation on the indicator disc.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Loosen screws [2] and remove cover [1] from the switch compartment. 9.7. Mechanical position indicator: set Move valve to end position CLOSED. Turn lower indicator disc until symbol (CLOSED) is in alignment with the mark on the cover.
Page 48
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it correctly. Place cover [1] on switch compartment. Fasten screws [2] evenly crosswise.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action Corrective action 10.1. Faults during commissioning Table 9: Faults during commissioning Fault description Possible causes Remedy Mechanical position indicator Reduction gearing is not suitable for Set gear stage of the reduction gearing.
Page 50
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Indication on display Description/cause Remedy Internal warning Collective signal 15: Press push button Details to display a list Device warnings of individual indications. The device can still be operated with restric- tions.
Page 51
Selector switch is not in position REMOTE. Set selector switch to position REMOTE. Service active Operation via service interface (Bluetooth) and Exit service software. service software AUMA CDT. Disabled Actuator is in operation mode Disabled. Check setting and status of function <Local controls enable>.
10.3.1. Fuses within the actuator controls Fuses used Primary fuses on power supply unit F1/F2 G fuse F1/F2 AUMA art. no. Size 6.3 x 32 mm Reversing contactors 1 A T; 500 V K002.277 Power supply ≤ 500 V Reversing contactors 2 A FF;...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action Loosen screws [1] and remove plug/socket connector [2]. Pull fuse holder [3] out of pin carrier, open fuse cover and replace old fuses by new ones.
Page 54
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Status indication S0007 displays a fault. The fault Thermoswitch is displayed when selecting Details. The motor has to cool down before the operation can be resumed. Depending on the parameter setting, the fault signal is either automatically reset or the fault signal has to be reset using the push button Reset in selector switch position LOCAL.
Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offer extensive service such as servicing and maintenance as well as customer Service & Support product training. For the relevant contact addresses, please refer to <Addresses>...
Page 56
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Servicing and maintenance AC 01.2 Non-Intrusive Observe the national regulations for waste disposal.
The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at http://www.auma.com in German and English (indication of commission number required).
Reversing contactors (mechanically and electrically interlocked) for motor power up to power class A1 Options: Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators) for AUMA power class B1 Control Standard: Via digital inputs OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, OPEN, STOP,...
Page 59
Bluetooth class II chip, version 2.0 with a range up to 10 m in industrial environments. Supports Communication interface the SPP Bluetooth profile (Serial Port Profile). Programming software: AUMA CDT, commissioning and diagnostic tool for windows based PCs, PDAs and smart phones...
Page 60
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Technical data AC 01.2 Non-Intrusive Application functions Standard: Switch-off mode adjustable Limit or torque seating for end position OPEN and end position CLOSED Torque by-pass, adjustable up to 5 seconds (no torque monitoring during this time) Start and end of stepping mode as well as ON and OFF time (1 up to 1,800 seconds) can be programmed individually for directions OPEN and CLOSE.
Refer to name plate The reversing contactors are designed for a lifetime of 2 million starts. For the assignment of AUMA power classes, please refer to electrical data on actuator. All input signals must be supplied with the same potential.
Finish coating Powder coating Colour Standard: AUMA silver-grey (similar to RAL 7037) Lifetime AUMA part-turn actuators meet or even exceed the lifetime requirements of EN 15714-2. Detailed information can be provided on request. Weight Refer to separate technical data 12.4.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Spare parts Spare parts 13.1. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2...
Page 64
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Spare parts 13.2. Actuator controls AUMATIC AC 01.2...
Page 66
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Certificates Certificates 14.1. Declaration of Incorporation and EC Declaration of Conformity...
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Index AC 01.2 Non-Intrusive Index Identification Indication lights Indications Accessories (electrical con- Indications on display nection) Indicator disc 36 , 47 Actual value - indication on Inspection record display Intermediate frame Actuator operation at the local Intermediate position indica-...
Page 69
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Index Packaging Valve position - indication on Parking frame display Password Password change Wall bracket Password entry Warnings - indication on dis- Positioner - indication on dis- play play Wiring diagram...
IBEROPLAN S.A. AUMA Polska Sp. z o.o. ES 28027 Madrid PL 41-219 Sosnowiec Tel +34 91 3717130 Tel +48 32 783 52 00 AUMA Riester GmbH & Co. KG iberoplan@iberoplan.com biuro@auma.com.pl www.auma.com.pl Plant Müllheim AUMA Finland Oy DE 79373 Müllheim FI 02230 Espoo AUMA-LUSA Representative Office, Lda.
Page 71
Tel + 673 3331269 / 3331272 Tel +968 24 636036 AUMA Argentina Rep.Office mikuni@brunet.bn r-negi@mustafasultan.com AR Buenos Aires Tel +54 11 4737 9026 AUMA Actuators (Tianjin) Co., Ltd. Beijing FLOWTORK TECHNOLOGIES contacto@aumaargentina.com.ar Branch CORPORATION CN 100020 Beijing PH 1550 Mandaluyong City AUMA Automação do Brazil ltda.
Page 72
AUMA Riester GmbH & Co. KG P.O.Box 1362 DE 79373 Muellheim Tel +49 7631 809 - 0 Fax +49 7631 809 - 1250 riester@auma.com www.auma.com Y005.955/003/en/3.13 For detailed information on AUMA products refer to the Internet: www.auma.com...
Need help?
Do you have a question about the SQ 05.2-F05 and is the answer not in the manual?
Questions and answers