Part-turn actuators, control unit: electronic (mwg) with actuator controls, aumatic ac 01.2 non-intrusive
Table of Contents

Advertisement

Part-turn actuators
SQ 05.2
SQ 14.2/SQR 05.2
SQR 14.2
Control unit: electronic (MWG)
with actuator controls
AUMATIC AC 01.2 Non-Intrusive
Control
Parallel
Profibus DP
Modbus
Foundation Fieldbus
Operation instructions
Assembly, operation, commissioning

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SQ 05.2-F05 and is the answer not in the manual?

Questions and answers

Summary of Contents for AUMA SQ 05.2-F05

  • Page 1 Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.2 Non-Intrusive Control Parallel Profibus DP Modbus Foundation Fieldbus Operation instructions Assembly, operation, commissioning...
  • Page 2: Table Of Contents

    This document contains information for installation, commissioning, operation and maintenance staff. It is intended to support device installation and commissioning. Reference documents: Manual (Operation and setting) AUMATIC AC 01.2 Parallel Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (refer to <Addresses>). Table of contents Page Safety instructions.........................
  • Page 3 Indications..........................7.1. Indications during commissioning 7.2. Indications in the display 7.2.1. Feedback indications from actuator and valve 7.2.2. Status indications according to AUMA classification 7.2.3. Status indications according to NAMUR recommendation 7.3. Mechanical position indicator/running indication 7.4. Indication lights Signals.............................
  • Page 4 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Table of contents AC 01.2 Non-Intrusive 11.2. Maintenance 11.3. Disposal and recycling Technical data......................... 12.1. Features and functions of actuator 12.2. Features and functions of actuator controls 12.3. Service conditions 12.4.
  • Page 5: Safety Instructions

    Any device modification requires prior consent of the manufacturer. 1.2. Range of application AUMA part-turn actuators are designed for the operation of industrial valves, e.g. butterfly valves and ball valves. Other applications require explicit (written) confirmation by the manufacturer. The following applications are not permitted, e.g.:...
  • Page 6: Applications In Ex Zone 22 (Option)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Safety instructions AC 01.2 Non-Intrusive Escalators Continuous duty Buried service Permanent submersion (observe enclosure protection) Potentially explosive areas, with the exception of zone 22 Radiation exposed areas in nuclear power plants No liability can be assumed for inappropriate or unintended use.
  • Page 7: References And Symbols

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Safety instructions Indicates a potentially hazardous situation with a low level of risk. Failure to observe this warning may result in minor or moderate injury. May also be used with property damage.
  • Page 8: Identification

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Identification AC 01.2 Non-Intrusive Identification 2.1. Name plate Each device component (actuator, controls, motor) is equipped with a name plate. Figure 1: Arrangement of name plates Actuator name plate Controls name plate Motor name plate Additional plate, e.g.
  • Page 9: Short Description

    This commission number can be used to directly download the wiring diagram (in German and English language), inspection records and further information regarding the device from the Internet: http://www.auma.com. For some details, the customer number might be required. Actuator serial number...
  • Page 10 (push buttons and display) and perform settings (contents of these instructions). read in or out data or modify and save settings via the AUMA CDT software (option), using a computer (laptop or PC). The connection between computer and AUMATIC is wireless via Bluetooth interface (not included in these instruc- tions).
  • Page 11: Transport, Storage And Packaging

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Transport, storage and packaging Transport, storage and packaging 3.1. Transport For transport to place of installation, use sturdy packaging. Hovering load! Risk of death or serious injury. Do NOT stand below hovering load.
  • Page 12: Assembly

    SQR 14.2 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Assembly 4.1. Mounting position AUMA actuators and actuator controls can be operated without restriction in any mounting position. 4.2. Handwheel fitting Information For transport purposes, handwheels from a diameter of 400 mm are supplied separ- ately.
  • Page 13 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Assembly Figure 6: Coupling fitting dimensions Coupling Valve shaft Grub screw Screw Table 2: Coupling fitting dimensions Type, size - output mounting flange X max [mm] Y max [mm] Z max [mm] SQ/SQR 05.2-F05...
  • Page 14: Mounting Positions Of Local Controls

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Fasten actuator with screws [4]. Information: We recommend applying liquid thread sealing material to the screws to avoid contact corrosion. Fasten screws [4] crosswise with a torque according to table. Table 3: Tightening torques for screws Screws Tightening torque T...
  • Page 15 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Assembly Electrostatic discharge ESD! Risk of damage to electronic components. Earth both operators and devices. Loosen screws and remove the local controls. Check whether O-ring is in good condition, correctly insert O-ring. Turn local controls into new position and re-place.
  • Page 16: Electrical Connection

    The pertaining wiring diagram/terminal plan (in German and English language) is plan attached to the device in a weather-proof bag, together with these operation instructions. It can also be obtained from AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com). Permissible networks...
  • Page 17: Connection With Auma Plug/Socket Connector

    For connecting cables exposed to UV radiation (outdoor installation), use UV resistant cables. 5.2. Connection with AUMA plug/socket connector Cross sections AUMA plug/socket connector: Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid PE connection : max.
  • Page 18: Terminal Compartment: Open

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive 5.2.1. Terminal compartment: open Figure 10: Connection AUMA plug/socket connector, version S Cover Screws for cover O-ring Screws for socket carrier Socket carrier Cable entry...
  • Page 19 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Electrical connection Remove cable sheathing. Strip wires. For flexible cables: Use end sleeves according to DIN 46228. Connect cables according to order-related wiring diagram. In case of a fault: Hazardous voltage while protective earth conductor is NOT connected! Risk of electric shock.
  • Page 20: Terminal Compartment: Close

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive 5.2.3. Terminal compartment: close Figure 13: Example: Version S Cover Screws for cover O-ring Screws for socket carrier Socket carrier Cable entry Blanking plug Cable gland (not included in delivery) Short-circuit due to pinching of cables! Risk of electric shock and functional failures.
  • Page 21: Parking Frame

    Observe prior to connec- tion We recommend: AUMA cable set LSW20. If the AUMA cable set is not used: Use suitable flexible and screened connecting cables. Use separate, CAN bus data cable for MWG of 120 Ohm character imped- ance (e.g. UNITRONIC BUS-FD P CAN UL/CSA - 2 x 2 x 0.5 mm², man- ufacturer: Lapp).
  • Page 22: Protection Cover

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Figure 15: Parking frame 5.3.3. Protection cover Protection cover for plug compartment when plug is removed. The open terminal compartment can be closed using a protective cover (not illustrated).
  • Page 23: Operation

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation Operation Valve damage due to incorrect basic setting! Prior to electrical operation of the actuator, the basic settings i.e. type of seating, torque and limit switching have to be completed. 6.1.
  • Page 24: Actuator Operation From Remote

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Figure 18: Local controls Push button for operation command in direction OPEN Push button STOP Push button for operation command in direction CLOSE Push button RESET Selector switch Hot surfaces, e.g.
  • Page 25: Menu Layout And Navigation

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation The bottom row of the display [6] serves as navigation support and explains which push buttons [1 4] are used for menu navigation. Figure 19: [1 4] Push buttons or navigation support Selector switch Display...
  • Page 26: User Level, Password

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Figure 21: Marking with ID ID starts with = status menu ID starts with = main menu It is possible to select between status menu S and main menu M: Group selection For this, set selector switch to 0 (OFF), hold down push button C for approx.
  • Page 27: Password Entry

    Default factory password: 0000 Service (5) Service staff Change configuration settings AUMA (6) AUMA administrator 6.4.1. Password entry Select desired menu and hold down push button for approx. 3 seconds. Display indicates the set user level, e.g Observer (1) Press Up ▲to select a higher user level and press...
  • Page 28: Language In The Display

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Select parameter Change passwords either: Change passwords click via the menu to parameter, or via direct display: press and enter ID M0229 Display indicates: ▶ Change passwords The user level is indicated in the top row (1 6), e.g.: For user level 1 (view only), passwords cannot be changed.
  • Page 29 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation Enter password (→ enter password). Display indicates: ▶ Language and Save (bottom row) Language selection 10. Select new language via Up ▲ Down ▼ resulting in the following significa- tions: black triangle: ▶...
  • Page 30: Indications

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Indications 7.1. Indications during commissioning When switching on the power supply, all LEDs on the local controls illuminate for LED test approx. 1 second. This optical feedback indicates that the voltage supply is connected to the controls and all LEDs are operable.
  • Page 31: Feedback Indications From Actuator And Valve

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications Figure 29: Information in the status bar (top) Operation mode Error symbol (only for faults and warnings) ID number: S = Status page If further details or information are available with reference to the display, the following Navigation support indications Details or More appear in the navigation support (bottom display row).
  • Page 32 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Torque (S0002) The indication is only available if the actuator is equipped with an MWG (magnetic limit and torque transmitter). S0002 on the display indicates the torque applied at the actuator output. The bargraph display appears after approx.
  • Page 33 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications If the positioner is enabled and activated, the bargraph indication for E1 (position Setpoint control setpoint) is displayed. The direction of the operation command is displayed by an arrow above the bargraph indication.
  • Page 34: Status Indications According To Auma Classification

    (P1, P2, ...) selected position (1, 2, ...) ) no position selected Actual position value 7.2.2. Status indications according to AUMA classification These indications are available, if the parameter Diagnostic classific. M0539 is set to AUMA. Warnings (S0005) If a warning has occurred, the display shows S0005: the number of warnings occurred a blinking question mark after approx.
  • Page 35: Status Indications According To Namur Recommendation

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications Figure 41: Fault For further information, please also refer to <Corrective action>. 7.2.3. Status indications according to NAMUR recommendation These indications are available, if the parameter Diagnostic classific. M0539 is set to NAMUR.
  • Page 36: Mechanical Position Indicator/Running Indication

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Figure 44: Maintenance required For further information, please also refer to <Corrective action>. Failure (S0011) The S0011 indication shows the causes of the failure indication according to NAMUR recommendation NE 107.
  • Page 37: Indication Lights

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications 7.4. Indication lights Figure 47: Arrangement and signification of indication lights Marking with symbols (standard) Marking with figures 1 6 (option) End position CLOSED reached (blinking: for operation in direction CLOSE) 2 Tc Torque fault CLOSE Motor protection tripped 4 To Torque fault OPEN...
  • Page 38: Signals

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Signals AC 01.2 Non-Intrusive Signals 8.1. Status signals via output contacts (digital outputs) Output contacts are used to send status signals (e.g. reaching the end positions, Characteristics selector switch position, faults...) as binary signals to the control room. Status signals only have two states: active or inactive.
  • Page 39: Commissioning (Basic Settings)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated.
  • Page 40: End Stop Closed: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Figure 48: End stop Screw plug for end stop OPEN Setting screw for end stop OPEN Screw plug for end stop CLOSED Setting screw for end stop CLOSED Dimensions/sizes 05.2 07.2...
  • Page 41: Type Of Seating: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) If the valve end position is not reached: Slightly turn setting screw [2] counterclockwise until valve end position OPEN can be safely set. Turning the setting screw [2] clockwise results in a smaller swing angle.
  • Page 42: Torque Switching: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Press Display indicates the current setting: Limit or Torque The bottom row of the display indicates either: Edit → continue with step 6 Save →...
  • Page 43 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Select parameter either: Select parameter click via the menu to parameter, or via direct display: press and enter ID M0088. Display indicates: Trip torque CLOSE Up ▲...
  • Page 44: Limit Switching: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive 9.4. Limit switching: set Valve damage at valve/gearbox due to incorrect setting! When setting with motor operation: Stop actuator before reaching end of travel (press push button STOP).
  • Page 45: Test Run

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Re-set end position CLOSED: Set end position CLOSED CMD0009 9.1 For large strokes: Set selector switch in position Local control (LOCAL) and operate actuator in motor operation via push button (CLOSED) in direction of the end position.
  • Page 46: Direction Of Rotation: Check

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive 9.5.1. Direction of rotation: check Move actuator manually to intermediate position or to sufficient distance from end position. Switch on actuator in direction CLOSE and observe the direction of rotation on the indicator disc.
  • Page 47: Mechanical Position Indicator: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Loosen screws [2] and remove cover [1] from the switch compartment. 9.7. Mechanical position indicator: set Move valve to end position CLOSED. Turn lower indicator disc until symbol (CLOSED) is in alignment with the mark on the cover.
  • Page 48 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it correctly. Place cover [1] on switch compartment. Fasten screws [2] evenly crosswise.
  • Page 49: Corrective Action

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action Corrective action 10.1. Faults during commissioning Table 9: Faults during commissioning Fault description Possible causes Remedy Mechanical position indicator Reduction gearing is not suitable for Set gear stage of the reduction gearing.
  • Page 50 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Indication on display Description/cause Remedy Internal warning Collective signal 15: Press push button Details to display a list Device warnings of individual indications. The device can still be operated with restric- tions.
  • Page 51 Selector switch is not in position REMOTE. Set selector switch to position REMOTE. Service active Operation via service interface (Bluetooth) and Exit service software. service software AUMA CDT. Disabled Actuator is in operation mode Disabled. Check setting and status of function <Local controls enable>.
  • Page 52: Fuses

    10.3.1. Fuses within the actuator controls Fuses used Primary fuses on power supply unit F1/F2 G fuse F1/F2 AUMA art. no. Size 6.3 x 32 mm Reversing contactors 1 A T; 500 V K002.277 Power supply ≤ 500 V Reversing contactors 2 A FF;...
  • Page 53: Motor Protection (Thermal Monitoring)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action Loosen screws [1] and remove plug/socket connector [2]. Pull fuse holder [3] out of pin carrier, open fuse cover and replace old fuses by new ones.
  • Page 54 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Status indication S0007 displays a fault. The fault Thermoswitch is displayed when selecting Details. The motor has to cool down before the operation can be resumed. Depending on the parameter setting, the fault signal is either automatically reset or the fault signal has to be reset using the push button Reset in selector switch position LOCAL.
  • Page 55: Servicing And Maintenance

    Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offer extensive service such as servicing and maintenance as well as customer Service & Support product training. For the relevant contact addresses, please refer to <Addresses>...
  • Page 56 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Servicing and maintenance AC 01.2 Non-Intrusive Observe the national regulations for waste disposal.
  • Page 57: Technical Data

    The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at http://www.auma.com in German and English (indication of commission number required).
  • Page 58: Features And Functions Of Actuator Controls

    Reversing contactors (mechanically and electrically interlocked) for motor power up to power class A1 Options: Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators) for AUMA power class B1 Control Standard: Via digital inputs OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, OPEN, STOP,...
  • Page 59 Bluetooth class II chip, version 2.0 with a range up to 10 m in industrial environments. Supports Communication interface the SPP Bluetooth profile (Serial Port Profile). Programming software: AUMA CDT, commissioning and diagnostic tool for windows based PCs, PDAs and smart phones...
  • Page 60 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Technical data AC 01.2 Non-Intrusive Application functions Standard: Switch-off mode adjustable Limit or torque seating for end position OPEN and end position CLOSED Torque by-pass, adjustable up to 5 seconds (no torque monitoring during this time) Start and end of stepping mode as well as ON and OFF time (1 up to 1,800 seconds) can be programmed individually for directions OPEN and CLOSE.
  • Page 61: Service Conditions

    Refer to name plate The reversing contactors are designed for a lifetime of 2 million starts. For the assignment of AUMA power classes, please refer to electrical data on actuator. All input signals must be supplied with the same potential.
  • Page 62: Accessories

    Finish coating Powder coating Colour Standard: AUMA silver-grey (similar to RAL 7037) Lifetime AUMA part-turn actuators meet or even exceed the lifetime requirements of EN 15714-2. Detailed information can be provided on request. Weight Refer to separate technical data 12.4.
  • Page 63: Spare Parts

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Spare parts Spare parts 13.1. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2...
  • Page 64 Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
  • Page 65: Actuator Controls Aumatic Ac

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Spare parts 13.2. Actuator controls AUMATIC AC 01.2...
  • Page 66 Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
  • Page 67: Certificates

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Certificates Certificates 14.1. Declaration of Incorporation and EC Declaration of Conformity...
  • Page 68: Index

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Index AC 01.2 Non-Intrusive Index Identification Indication lights Indications Accessories (electrical con- Indications on display nection) Indicator disc 36 , 47 Actual value - indication on Inspection record display Intermediate frame Actuator operation at the local Intermediate position indica-...
  • Page 69 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Index Packaging Valve position - indication on Parking frame display Password Password change Wall bracket Password entry Warnings - indication on dis- Positioner - indication on dis- play play Wiring diagram...
  • Page 70: Addresses

    IBEROPLAN S.A. AUMA Polska Sp. z o.o. ES 28027 Madrid PL 41-219 Sosnowiec Tel +34 91 3717130 Tel +48 32 783 52 00 AUMA Riester GmbH & Co. KG iberoplan@iberoplan.com biuro@auma.com.pl www.auma.com.pl Plant Müllheim AUMA Finland Oy DE 79373 Müllheim FI 02230 Espoo AUMA-LUSA Representative Office, Lda.
  • Page 71 Tel + 673 3331269 / 3331272 Tel +968 24 636036 AUMA Argentina Rep.Office mikuni@brunet.bn r-negi@mustafasultan.com AR Buenos Aires Tel +54 11 4737 9026 AUMA Actuators (Tianjin) Co., Ltd. Beijing FLOWTORK TECHNOLOGIES contacto@aumaargentina.com.ar Branch CORPORATION CN 100020 Beijing PH 1550 Mandaluyong City AUMA Automação do Brazil ltda.