Operation Via Hart Configuration Tool (Hart 7); Hart Protocol Revision; Device Description (Dd) On A Hart Configuration Tool And Axr Device Revision; Dd Revision And Device Revision - YOKOGAWA ADMAG AXR User Manual

Two-wire magnetic flowmeter integral flowmeter
Table of Contents

Advertisement

9.

OPERATION VIA HART CONFIGURATION TOOL (HART 7)

This Chapter describes the device (AXR) operation
procedures using a HART configuration Tool (such
as FieldMate).
NOTE
For more details regarding the operations for
the HART configuration tool, read the HART
configuration tool operations manual.
Note: HART is a registered trademark of the
FieldComm Group.
9.1

HART Protocol Revision

For the models with the output signal code "-J",
HART protocol revision 5 or 7 is selectable. The
protocol revision is set as specified in the order.
How to confirm protocol revision is shown below.
There are two ways to confirm the protocol revision
set to the transmitter.
(1) Confirmation by the name plate
The HART protocol revision at the time of
shipment is shown by the last number at the
serial number column of the name plate.
(2) Confirmation by using HART configuration tool
Follow the procedure below.
1) C onnect the configuration tool to the device.
2) Call up "Review4" display.
[Root Menu] → Review → Review4
3) HART protocol revision is displayed on the
"Universal rev" column.
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
XXX...XX 
5: HART 5
7: HART 7
F0901.ai
IMPORTANT
Protocol revision supported by HART
configuration tool must be the same or higher
than that of the device.
Protocol revision of
the device
 : Communication OK
× : Communication NG
NOTE
• In this User's Manual, HART protocol
revision 5 and 7 are described as HART 5
and HART 7 respectively.
• HART 7 communication is supported by
FieldMate R2.04 or later.
NOTE
When the output signal code of the device is "-J",
HART protocol revision can be changed. Read
Subsection 9.8.5 about the procedure of the
revision change of HART 5 and HART 7.
9.2
Device Description (DD) on
a HART Configuration Tool
and AXR Device Revision

9.2.1 DD Revision and Device Revision

Before using the HART Configuration Tool (such
as FieldMate), confirm that the DD (Device
Description) of the AXR is installed in the
Configuration Tool before using.
• AXR: HART 7
• Device type: 0x3757
• Device Revision: 10
• DD Revision: 1
The DD revisions for AXR and Configuration Tool's
can confirm in accordance with the following steps.
If the correct DD is not installed in the HART
9-1
Protcol revision
supported by HART
configuration tool
5
7
5
7
×
IM 01E30D01-01EN