YOKOGAWA ADMAG AXR User Manual page 28

Two-wire magnetic flowmeter integral flowmeter
Table of Contents

Advertisement

For working on the electric wire tubes or the flexible
tubes (G1/2), remove the waterproof gland and
attach them directly to the wiring port.
Washer
Gasket
Waterproof gland
Cable
Figure 4.3.1 Waterproof Gland (Optional code EG)
Gasket
G1/2
Tightening gland
Cable
When working on conduit pipes or flexible pipes (G1/2 only)
Figure 4.3.2 Waterproof Gland with Union Joint
(Optional code EU)
Gasket
Plastic gland
Figure 4.3.3 Plastic Gland (Optional code EP)
F0403.ai
Washer
F0404.ai
F0405.ai
<4. WIRING>
(3) Conduit Wiring
When wiring the conduits, pass the conduit
through the wiring connection port, and utilize the
waterproof gland to prevent water from flowing in.
Place the conduit pipe on an angle as shown in
Figure 4.3.4. Install a drain valve at the low end of
the vertical pipe, and open the valve regularly.
Drain valve
Figure 4.3.4 Conduit Wiring
4-3
F0406.ai
IM 01E30D01-01EN