YOKOGAWA ADMAG AXR User Manual page 34

Two-wire magnetic flowmeter integral flowmeter
Table of Contents

Advertisement

Selection of HART 5/ HART 7
Output Signal
-E
Code
Ordering
Information
HART Protocol
Revision
Require-
ment for
HART 7
function-
ality
Selec-
tion
guide
Not avail-
able to
Other
switch to
condi-
HART 7
tions
protocol
after deliv-
ery.
Remarks
Note 1
Note 1: "-E" is HART5 exclusive model and will be terminated.
"-J" is recommended for HART communication.
Note 2: HART protocol revision for the device and HART
configuration tool
HART 7 communication is supported by FieldMate
R2.04 or later.
Protocol revision supported by HART
AXR, HART 5
Available
AXR, HART 7
Not available
(2) Pulse Output, Status Output, Alarm Output
One Output can be selected from pulse, alarm, or
status through the parameter setting.
Read Table 4.6.2 or Table 4.6.5 as wiring examples.
Digital Output:
Transistor contact output, open collector
Contact rating: 30 V DC, 120 mA DC
Low level: 0 to 2 V DC (Read Figure 4.6.4)
HIGH level
LOW level
Figure 4.6.4 High and Low levels (transistor contact
output)
-J
Specify "5" Specify "7"
HART 5
HART 7
YES
Be sure to
confirm the
protocol
revision of
NO
the HART
configura-
tion tool
shown in
Note 2.
Available
Available
to switch
to switch
to HART
to HART
7 proto-
5 proto-
col after
col after
delivery by
delivery by
user-con-
user-con-
figuration.
figuration.
Note 2
Note 2
configuration tool
5
7
Available
Available
0 to 2 V
0 V
F0417.ai
<4. WIRING>
IMPORTANT
Precaution for Pulse Output
• As this is a transistor contact (insulated
type), give attention to proper voltage and
polarity when wiring.
• Do not apply a voltage larger than 30 V DC
or a current larger than 120 mA in order to
prevent damage to the instrument.
• When input filter constant of the electronic
counter is large in relation to the pulse width,
the signal will decrease and the count will not
be accurate.
• If the input impedance of the electronic
counter is large, an induction noise from
the power supply may result in inaccurate
counts. Use a shield cable or sufficiently
reduce the input impedance of the electronic
counter within the electromagnetic flowmeter
pulse output specification range.
• The load resistance for pulse output is
necessary. Read Table 4.6.3 or Table 4.6.6.
• Neither no load resistance nor too small
value of load resistance for pulse output will
give a damage to the instrument.
IMPORTANT
Precaution for Status Output and Alarm Output
• As this is a transistor contact (insulated
type), give attention to proper voltage and
polarity when wiring.
• Do not apply a voltage larger than 30V DC
or a current larger than 120 mA in order to
prevent damage to the instrument.
• This output cannot switch an AC load. To
switch an AC load, an intermediate relay
must be inserted as shown in Table 4.6.2 or
Table 4.6.5.
* The alarm output operates from open
(normal) to closed (alarm occurrence) in the
default value (as setup upon plant shipment).
Changes can be made via the parameter
settings.
4-9
IM 01E30D01-01EN