Configuration Tool, download them from the HART
official site, otherwise, contact the respective
vendors of the Configuration Tool for its upgrade
information.
1. Confirmation of the device revision for AXR
Connect the Configuration Tool to the AXR.
The device revision can be checked as follows.
[Root Menu] → Review → Review4 → Fld dev rev
2. Confirmation of the device revision for the
HART Configuration Tool
(1) Turn on the power of the Configuration Tool
under the standalone condition.
(2) Confirm the installed DD revision in
accordance with the procedure of the
Configuration Tool. Read its manual how to
confirm it in detail.
9.3 Interconnection between AXR and HART Configuration Tool
The HART Configuration Tool can interface with the AXR from the control room, the AXR site, or any other
wiring termination point in the loop, provided there is a minimum load resistance of 250 Ω between the
connection and the receiving instrument. To communicate, it must be connected in parallel with the AXR, and
the connections must be non-polarized. Figure 9.3 illustrates the wiring connections for a direct interface at the
AXR site. The HART Configuration Tool can be used for remote access from any terminal strip as well.
SUPPLY
DO
+
AXR
PC/FieldMate
Figure 9.3
Connecting the HART Communicator
WARNING
Be sure to set parameters as "Protect" on the
write protect function after finish of parameter
setting work.
Read Chapter 6 Menu P and Subsection 11.3.2,
how to use the write protect function in detail.
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
4 to 20 mA DC signal line
Relaying
terminals
USB
FieldMate
modem
PC/FieldMate
9.2.2 Device Type Manager (DTM) and
Device Revision
When configure the parameters using FieldMate,
use the DTM (Device Type Manager) reading the
following table.
MODEL
DTM
Name
AXR HART 7
AXR
DTM
The device revision can be checked as follows.
[Root Menu] → Review → Review4 → Fld dev rev
Control room
Terminal board
Receiving
instrument
load resistance:
USB
PC/FieldMate
IMPORTANT
If the power of flowmeter is turned off within 30
seconds after parameters have been set, these
settings will be canceled. Accordingly, please
keep the power on for at least 30 seconds after
setting parameters.
9-2
Device
Device
Type
Revision
AXR
10
(0x3757)
Distributor
250 to 600 Ω
F0903.ai
IM 01E30D01-01EN