(4) Item D (Menu D): Total Setting items
Menu D contains setting items such as the totalization scale and the forward/reverse totalized values.
Name
Item
R/W
Display unit
(BRAIN)
D00 Total Set
(TOTAL SET)
D10 Total Unit
(TOTAL UNIT)
D11 Total Scale
(TOTAL SCALE)
D12 Total Decimal Pnt
(TL DECIMAL)
D13 Total Low Cut
(TOTAL LOWCUT)
D14 Total Rate Check
(TL RATE CHK)
D20 Total Execution
(TOTAL EXEC)
D21 Ttl Set Val Lower
(TL SET VAL L)
D22 Ttl Set Val Upper
(TL SET VAL U)
D23 Ttl Switch Lower
(TL SWITCH LO)
D24 Ttl Switch Upper
(TL SWITCH UP)
D30 Ttl User Select
(TL USER SEL)
D31 Ttl User Unit
(TL USER UNIT)
D60 —
(SELF CHECK)
Data range
Units
Display unit
/BRAIN
W
n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
W
0 to 32000
D10
(B30)
W
0
1
2
3
4
5
6
7
W
0 to 100
R
0 to 999999
Pulse/s
W
Start
Stop
Preset Total
Preset Rev Total
W
0 to 999999
W
0 to 99
W
0 to 999999
W
0 to 99
W
No
Yes
W
8 alphanumeric
characters
R
Good
Error
<6. PARAMETER DESCRIPTION>
Position
Default value
of decimal
(*): Indicated item
point
Pulse/s (*)
0 to 4
0 (*)
0
%
0
3 %
0 to 5
0.0
Start
0
0
0
0
0
0
0
0
No
6-6
Description
Selects the flow rate unit
per one pulse as used for
totalization display. Linked with
B30.
Sets the flow rate per one pulse
as used for totalization display.
Linked with B31.
Selects position of decimal
point for totalization display
Sets the range in vicinity of 0%
within which the totalization
display will be halted.
Displays the totalization rate in
"Pulse/s"
Executes "Start" or "Stop" of
the totalization function, or
executes "Preset Total" or
"Preset Rev Total".
Sets the totalization preset
value in the lower 6 digits of the
8-digit totalized value.
Sets the totalization preset
value in the upper 2 digits of
the 8-digit totalized value.
Sets the totalization switch
value in the lower 6 digits of the
8-digit totalized value.
Sets the totalization switch
value in the upper 2 digits of
the 8-digits totalized value.
Selects whether or not special
units are used as totalized
units.
Sets the special totalized units.
Read Section 6.5 "Alarm
Functions".
IM 01E30D01-01EN