YOKOGAWA ADMAG AXR User Manual page 60

Two-wire magnetic flowmeter integral flowmeter
Table of Contents

Advertisement

(7) Item G (Menu G): Alarm Setting items
Menu G contains setting items relevant to alarm output, burnout, alarm record, etc.
Name
Item
R/W
Display unit
(BRAIN)
G00 Alarm
(ALARM)
G10 Low Alarm
(LOW ALARM)
G11 High Alarm
(HIGH ALARM)
G12 H/L Alarm Hys
(H/L ALM HYS)
G20 4-20 System Alm
(4-20 SYS ALM)
G25 4-20 Process Alm
(4-20 PRO ALM)
G26 Alm-Sig Over
(ALM-SIG OVER)
G27 Alm-Emp Pipe
(ALM-EMP PIPE)
G28 Alm-H/L
(ALM-H/L)
G29 Alm-Adhesion
(ALM-ADHESION)
G30 4-20 Setting Alm
(4-20 SET ALM)
G31 Alm-Setting
(ALM-SETTING)
G35 Alarm Display
(ALM DISPLAY)
G40 Operation Time
(OPERATE TIME)
G41 Alm Record1
(ALM RECORD1)
Data range
Units
Display unit
/BRAIN
W
-105 to 105
W
-105 to 105
W
0 to 10
R
21.6mA (Read IM)
3.2mA (Read IM)
W
21.6mA or More
20.5mA
Hold
4.0mA
3.8mA
3.2mA or Less
W
No
Yes
W
No
Yes
W
No
Yes
W
No
Yes
W
21.6mA or More
20.5mA
Hold
4.0mA
3.8mA
3.2mA or Less
W
No
Yes
W
Normal
NE107
R
0D 00:00 to
9999D 23:59
R
10:uP Fault
11:EEPROM Fault
12:Sub uP Fault
13:EX Pwr Fault
14:A/D(S) Fault
15:A/D(I) Fault
16:Analog Fault
17:Coil Open
18:Coil Short
19:Excite Error
20:Pulse Error
21:EEPROM Dflt
22:Power Off
23:Inst Pwr Fail
28:WDT
30:Sig Overflow
31:Empty Pipe
33:Adhesion Alm
91:Disp Cur Wng
<6. PARAMETER DESCRIPTION>
Position
Default value
of decimal
(*): Indicated item
point
%
0
-105%
%
0
105%
%
0
5 %
21.6mA (Read IM)
(*)
21.6mA or More (*) Selects the current output
Yes
No
No
No
21.6mA or More (*) Selects the current output
Yes
Normal
6-9
Description
Sets level setting value for low
flow rate limit (L)
Sets level setting value for high
flow rate limit (H)
Sets hysteresis width for high-
low flow rate limit alarm
Displays the current output
during a system alarm
occurrence
during a process alarm
occurrence
Selects whether a signal
overflow alarm is to be
specified as an alarm.
Selects whether an empty pipe
alarm is to be specified as an
alarm.
Selects whether a flow rate
high or low alarm is to be
specified as an alarm.
Selects whether an electrode
adhesion alarm is to be
specified as an alarm.
during a setting alarm
occurrence
Selects whether a setting alarm
is to be specified as an alarm.
Selects alarm display form
on the display unit and
configuration tools.
Operation time
Displays the content of the
most recent alarm.
IM 01E30D01-01EN