 Intrinsically safety circuit
• Maximum Voltage (Uo): 14 V
• Maximum Current (Io): 17 mA
• Maximum Electrical Power (Po): 0.12 W
 Fluid Temperature: –20 to 130°C
 Ambient Temperature: –20 to 55°C
 Grounding:
Grounding resistance of 10 Ω or less is
necessary for class A grounding terminal.
Grounding resistance of 100 Ω or less is
necessary for Functional grounding terminal.
When the optional code A is selected,
grounding resistance of 10 Ω or less shall be
required.
IMPORTANT
Class A grounding should be installed in non-
hazardrous area.
 Flameproot packing adapter:
The specifying optional code G11 is necessary.
In case of two flameproof packing adapters,
select optional code G32 with G11.
(2) Wiring Installation
For the external wiring of flameproof types, use
a flameproof packing adapter (optional code
G11, G32) approved by Yokogawa (Read Figure
14.5.2) (Read "INSTALLATION AND OPERATING
PRECAUTIONS FOR TIIS FLAMEPROOF
EQUIPMENT" at the end of this manual).
WARNING
Available only for wiring of using a flameproof
packing adapter approved by Yokogawa.
The flameproof metal conduit wiring for TIIS
flameproof type is not permitted.
(2-1) Wiring Cable through Flameproof Packing
Adapter
WARNING
For the TIIS flameproof type with wiring using a
flameproof packing adapter, wire cables through
the packing adapters approved by Yokogawa
(optional code G11, G32).
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>
18(0.71)
*Packing
(Choose from the table below
depend on cable outside diameter)
Nominal diameter
T1
T2
G 1/2
G 1/2
Figure 14.5.1 Flameproof Packing Adapter
• Apply a nonhardening sealant to the terminal
box connection port and to the threads on the
flameproof packing adapter for waterproofing.
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Figure 14.5.2 Typical Wiring Using Flexible Metal
Follow the procedure for flameproof packing
adapter setting. (Read Figure 14.5.3)
Before fighting, confirm cable length from
terminal to flameproof packing adapter when
setting. Once it is tightened, loosening and re-
tightening may damage its sealing performance.
T1
Adapter body(M. Screw)
O-Ring
Packing case
16.5(0.65)
Hexagon socket set screw
Packing *
Hexagon socket set screw
O-Ring
L
F
O-Ring
G
Washer
Union nut
Packing gland
Clamp ring
Clamp nut
T2
O-Ring
B.coupling
Cable(user's scope)
Dimension
Packing diameter
Cable outer
diameter
C
D
L
F
ø8.0 to ø10.0
ø10.0(0.39)
(0.31 to 0.39)
35
39
94.5
(1.38)
(1.54)
(3.72)
(0.79)
ø10.0 to ø12.0
ø12.0(0.47)
(0.39 to 0.47)
Flameproof
packing adapter
Apply a
non-hardening
sealant to the threads
for waterproofing.
Conduit
CAUTION
14-9
Unit : mm
(Approx. inch)
C
D
F1406.ai
Identifi-
Weight
cation
kg
Parts No.
G
mark
(lb)
16 8-10
ø20.0
0.26
G9601AM*
(0.57)
16 10-12
*: G 11: 1 unit
G 11 with G 32: 2 units
F1407.ai
IM 01E30D01-01EN