e)
Burst Mode
When the Burst mode is set to "Wired HART
Enabled", the transmitter starts to send the data.
• Procedure to call up the display
DD
[Root Menu] → Detailed setup →
DTM
HART output → Burst condition →
Burst Message 1,2 or 3 → Burst
mode → Wired HART Enabled
IMPORTANT
In case of using HART7 Burst communication,
use Burst Message 1 in following settings:
Contents
Menu
c) Update
Set Burst Period 0.5 s (Default)
Period
d) Burst Msg
Burst Msg
Trigger Mode
Trigger Mode
e) Burst mode
Burst mode
(3) Event Notification
When a setting change and a change of the Self-
diagnostics occur, device detect it as an event and
can transmit an alarm signal continuously.
Up to four events that occurred can be stored.
When using this function, set to Burst mode as
"Wired HART Enabled".
(3-1)
Set Event Notification
• Procedure to call up the display
DD
[Root Menu] → Detailed setup
DTM
→HART output → Burst
condition → Event Notification →
→ Event Mask
Set the status to detect
→ E vent
Set the retry time when the event
Notification
occur.
Retry Time
→ M ax Update
Set the retry time when the event
Time
does not occur.
→ E vent Debounce
The setting of the minimum event
Interval
duration
→ E vent
Stop the event monitor: Off
Notification
Shift to the monitor state: Enable
Control
event notification on token-
passing data link layer
a)
Event Mask
Set the status to detect in the Event Mask
parameter.
Status group 1 Mask to 7 Mask
Device Status Mask
Ext dev status Mask
Device Diagnostic Status 0 Mask
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
Value
Continuous
(Default)
Wired HART
Enabled
b) Event Notification Retry Time/ Max Update
Time/ Event Debounce Interval
Set to Event Notification Retry Time, Max Update
Time and Event Debounce Interval.
For Event Notification Retry Time, set the value
that is smaller than Max Update Time.
Event Notification
Retry Time
/Max Update Time
---
Off
0.5 s
0.5 s
1 s
1 s
2 s
2 s
4 s
4 s
8 s
8 s
16 s
16 s
32 s
32 s
1 min
1 min
5 min
5 min
10 min
10 min
15 min
15 min
30 min
30 min
45 min
45 min
60 min
60 min
c) Event Notification Control
Select "Enable event notification on token-passing
data link layer" in the Event Notification Control
parameter to shift to the monitor state:
(3-2)
Acknowledge Event Notification (DTM
only)
The transmission of the event message stops when
event is approved.
• Procedure to call up the display
DTM
[Root Menu] → Detailed
setup →HART output → Burst
condition → Event Notification
→ Event Knowledge →
→ A cknowledge
Acquisition of the event number
Event Notification
and approval.
a)
Get Event Number
Confirm the latest event number.
Execute Acknowledge Event Notification
method.
1) Set "Enter Event Number" to "0".
2) OK.
3) Set "Select Transaction" to "Trans 0: Read
Event Notification".
4) OK.
5) Confirm "Event Number".