5.6

BRAIN Configuration Tool

The connection of the BRAIN configuration tool
(BRAIN TERMINAL (BT200) or FieldMate (Versatile
Device Management Wizard)) is shown as below.
Read the user's manual of BT200 (IM 01C00A11-01E)
for the operation, and the user's manual of BRAIN
communication type as listed in Table 1.1 for the detailed
parameter setting via BRAIN communication.
The communication signal is superimposed onto the 4 to
20 mA DC analog signal to be transmitted. The BRAIN
configuration tool can interface with this device from
the control room, this device site, or any other wiring
termination point in the loop, provided there is a minimum
load resistance of 250 Ω between the connection and the
receiving product.
To communicate, it must be connected in parallel with this
device, and the connections must be non-polarized. See
Figure 5.6.
4 to 20 mA DC
Signal
Relaying
Transmission Line
Terminals
Iout+
Iout-
Magnetic Flowmeter
Terminal Box
USB
FieldMate
Modem
USB
PC/FieldMate
BT200
Figure 5.6 Connecting the BRAIN Configuration Tool
IMPORTANT
Communication signal is superimposed on analog
output signal. It is recommended to set a low-pass
filter (approximately 0.1s) to the receiver in order to
reduce the output effect from communication
signal. Before online-communication, confirm that
communication signal does not give effect on the
upper system.
IMPORTANT
Restrictions exist with regard to the distance over
which communication is possible. Read the general
specifications as listed in Table 1.1.
For explosion protection type, the configuration tool
should be connected at the safe site of "no explosive
atmosphere".
<5. Basic Operating Procedures>
5.7
The connection of the HART configuration tool
(FieldMate (Versatile Device Management Wizard))
is shown as below. Read the user's manual of HART
communication type as listed in Table 1.1 for the
detailed parameter setting via HART communication.
• For more details regarding the operations of the
• When using FieldMate, be sure that the revision is
Perameters on HART configuration tool are displayed
in English only. Even if any language other than
Control Room
English is selected as "display language" from display
Terminal
Distributor
Board
panel, parameters are displayed in English on HART
configuration tool.
Load
Resistance
250 to 450 Ω
5.7.1 Connections with HART Configura-
The HART configuration tool can interface with this
device from the control room, this device site, or any
F0529.ai
other wiring termination point in the loop, provided there
is a minimum load resistance of 230 Ω between the
connection and the receiving product. To communicate,
it must be connected in parallel with this device, and the
connections must be non-polarized.
Read Figure 5.7.
Iout+
Iout-
Magnetic Flowmeter
Terminal Box
Figure 5.7
Communication signal is superimposed on analog
output signal. It is recommended to set a low-pass filter
(approximately 0.1s) to the receiver in order to reduce
the output effect from communication signal. Before
online-communication, confirm that communication
signal does not give effect on the upper system.

HART Configuration Tool

NOTE
HART configuration tool, read the manual of HART
configuration tool.
R3.02.00 or later.
NOTE
tion Tool
4 to 20 mA DC
Signal
Relaying
Transmission Line
Terminals
USB
FieldMate
Modem
USB
PC/FieldMate
Connecting the HART Configuration Tool
IMPORTANT
54
Control Room
Terminal
Distributor
Board
Load
Resistance
230 to 600 Ω
F0530.ai
IM 01E24A01-01EN