(11) Item M (Menu M): Automatic Zero-Adjustment Function Setting items
Menu M contains items that are relevant to automatic zero adjustment.
Name
Item
R/W
Display unit
(BRAIN)
M00 Adjustment
(ADJUSTMENT)
M10 Auto Zero Exe
(AUTOZERO EXE)
M11 Autozero Time
(AUTOZ TIME)
M12 Flow Zero(IEL)
(FL ZERO(IEL))
M13 Flow Zero(IEM)
(FL ZERO(IEM))
M14 Flow Zero(IEH)
(FL ZERO(IEH))
M15 Flow Span Adjust
(FL SPAN ADJ)
M20 Adjustment 4mA
(ADJUST 4mA)
M21 Adjustment 20mA
(ADJUST 20mA)
M60 —
(SELF CHECK)
(12) Item N (Menu N): Loop Test Setting items
Menu N contains items that are relevant to the execution of loop testing.
Name
Item
R/W
Display unit
(BRAIN)
N00 Test
(TEST)
N10 Test Mode
(TEST MODE)
N11 Test Output Value
(TEST OUT VAL)
N12 Test DO
(TEST DO)
N15 Test Time
(TEST TIME)
N20 Test Iex
(TEST IEX)
N30 Flow Tube
(FLOW TUBE)
N40 Average Execution
(AVG EXEC)
N41 Average Timer
(AVG TIMER)
N42 Average Flow
(AVG FLOW)
N60 —
(SELF CHECK)
Data range
Units
Display unit
/BRAIN
W
No Execution
Execution
W
1 to 900
W
-99.999 to 99.999
W
-99.999 to 99.999
W
-99.999 to 99.999
W
0.4000 to 2.0000
W
-10.00 to 10.00
W
-10.00 to 10.00
R
Good
Error
Data range
Units
Display unit
/BRAIN
W
Normal
Test
W
-1 to 103
W
Open(Off)
Closed(On)
Pulse
W
10min
30min
60min
3h
6h
12h
W
Normal
Test (Iex OFF)
W
Detector
Calibrator
W
Stop
Start
W
1 to 600
R
-999999 to 999999
C40/C41
R
Good
Error
<6. PARAMETER DESCRIPTION>
Position
Default value
of decimal
(*): Indicated item
point
No Execution
s
0
450 s
3
0.000
3
0.000
3
0.000
4
1.0000
%
2
0.00 %
%
2
0.00 %
Position
Default value
of decimal
(*): Indicated item
point
Normal
%
0
0%
Open(Off)
30min
Normal
Detector
Stop
s
0
30 s
0 to 5
0.00000 m/s
6-14
Description
Selects whether or not
automatic zero adjustment is
carried out. Linked with B50.
Sets execution time for
automatic zero adjustment
Displays the result of automatic
zero adjustment (excitation
current (Low))
Displays the result of automatic
zero adjustment (excitation
current (Middle))
Displays the result of automatic
zero adjustment (excitation
current (High))
Sets adjustment factor of flow
span
Sets adjustment for 4mA output
Sets adjustment for 20mA
output
Read Section 6.5 "Alarm
Functions".
Description
Selects whether mode will be
set to "Normal" or "Test".
Sets the test output value.
Selects the test condition for
DO terminal.
Select the holding time of the
test mode
Selects the test of excitation
current
Selects type of operating
flowtube
Selects whether the execution
for measurement of averaged
flowrate is occurrence
Sets totalization time for
measurement of averaged
flowrate
Displays the averaged flowrate
Read Section 6.5 "Alarm
Functions".
IM 01E30D01-01EN