Timeslot information
■Timeslot 0 information (Un\G23552 to Un\G23567)
Cycle start offset (ns, s unit) of Timeslot 0 and cycle end offset (ns, s unit) are stored.
Address
Un\G23552 to Un\G23553
Un\G23554
Un\G23555
Un\G23556 to Un\G23557
Un\G23558
Un\G23559 to Un\G23567
■Timeslot 1 to 7 information (Un\G23568 to Un\G23679)
Timeslot 1 to 7 information is stored in the same order as Timeslot 0 information.
RX offset/size information
■RX offset/size information (Un\G23808 to Un\G24831)
The start number and the number of points of RX for each station are stored.
Address
Un\G23808 to Un\G23809
Un\G23810 to Un\G23811
Un\G23812 to Un\G23813
Un\G23814 to Un\G23815
Un\G24288 to Un\G24289
Un\G24290 to Un\G24291
Un\G24292 to Un\G24831
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 23808 + (station No.)  4
• Size buffer memory address = 23810 + (station No.)  4
RY offset/size information
■RY offset/size information (Un\G24832 to Un\G25855)
The start number and the number of points of RY for each station are stored.
Address
Un\G24832 to Un\G24833
Un\G24834 to Un\G24835
Un\G24836 to Un\G24837
Un\G24838 to Un\G24839
Un\G25312 to Un\G25313
Un\G25314 to Un\G25315
Un\G25316 to Un\G25855
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 24832 + (station No.)  4
• Size buffer memory address = 24834 + (station No.)  4
Name
Description
Cycle start offset (ns unit)
The ns digits of cycle start offset are stored.
Stored range: 0 to 999999999ns
Cycle start offset (s unit)
The s digits of cycle start offset are stored.
Stored range: 0 to 65535s
System area
Cycle end offset (ns unit)
The ns digits of cycle end offset are stored.
Stored range: 0 to 999999999ns
Cycle end offset (s unit)
The s digits of cycle end offset are stored.
Stored range: 0 to 65535s
System area
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.120 offset
Station No.120 size (in units of words)
System area
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.120 offset
Station No.120 size (in units of words)
System area