Error
Error definition and causes
code
3013H
The value set in "Transient Transmission
Time" in "Communication Period Setting"
under "Basic Settings" of the master
station is smaller than the transient
transmission time calculated using the
number of slave stations and the points of
slave stations set in "Network
Configuration Settings" under "Basic
Settings".
3014H
When "Communication Mode" under
"Application Settings" of the master station
is set to "Multicast", in the "Network
Configuration Settings" of the "Basic
Settings", "Communication Period Setting"
of the local station is set to "Normal-
Speed" or "Low-Speed".
3015H
The value set in "Communication Period
Interval Setting" in "Communication Period
Setting" under "Basic Settings" of the
master station is smaller than the
communication cycle interval calculated by
the number of stations and points of slave
stations that was set in "Network
Configuration Settings" under "Basic
Settings".
3016H
System error
3017H
The value set in "Cyclic transmission time"
in "Communication Period Setting" under
"Basic Settings" of the master station is
smaller than the cyclic transmission time
calculated by the number of stations and
points of slave stations set in "Network
Configuration Settings" under "Basic
Settings".
3018H
The value set in "Transient Transmission
Time" in "Communication Period Setting"
under "Basic Settings" of the master
station is smaller than the transient
transmission time calculated using the
number of slave stations and the points of
slave stations set in "Network
Configuration Settings" under "Basic
Settings".
Action
Set "Communication Period Interval Setting" and "Cyclic Transmission
Time" so that the value of "Transient Transmission Time" in "Communication
Period Setting" under "Basic Settings" of the master station is equal to or
larger than the value shown in the detailed information displayed in "Module
Diagnostics".
• Set "Communication Mode" in "Application Settings" of the master station
to "Unicast".
• In "Network Configuration Settings" under "Basic Settings" of the master
station, set "Communication Period Setting" of the local station to "Basic
Period".
Set the value of "Communication Period Interval Setting" as a value equal to
or larger than the value of "Communication Period Interval (Calculation
value)" (SW0072) of a local station using "Communication Period Setting"
under "Basic Settings" of the master station. ( Page 215
Communication cycle intervals)
Please consult your local Mitsubishi representative.
Set the value of "Cyclic Transmission Time" as a value equal to or larger
than the value of "Cyclic Transmission Time (Calculation value)" (SW0073)
of a local station using "Communication Period Setting" under "Basic
Settings" of the master station. ( Page 215 Communication cycle
intervals)
Set "Communication Period Interval Setting" and "Cyclic Transmission
Time" so that the value of "Transient Transmission Time" in "Communication
Period Setting" under "Basic Settings" of the master station is equal to or
larger than the value of "Transient Transmission Time (Calculation value)"
(SW0078) of a local station. ( Page 215 Communication cycle intervals)
Detailed
information 1
Detailed
information 2
■
■Communication
Period Interval
Information
• Transient
Transmission Time
(Calculation value:
s)
■Parameter
information
• Parameter type
• Intelligent module
No.
• Parameter No.
■Target station
information
• Station Number
• IP address
10 TROUBLESHOOTING
163
10.5 List of Error Codes
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5uMelsec iq-f fx5uc

Table of Contents