Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 194

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

RWw offset/size information
■RWw offset/size information (Un\G25856 to Un\G26879)
The start number and the number of points of RWw for each station are stored.
Address
Un\G25856 to Un\G25857
Un\G25858 to Un\G25859
Un\G25860 to Un\G25861
Un\G25862 to Un\G25863
Un\G26336 to Un\G26337
Un\G26338 to Un\G26339
Un\G26340 to Un\G26879
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 25856 + (station No.)  4
• Size buffer memory address = 25858 + (station No.)  4
RWr offset/size information
■RWr offset/size information (Un\G26880 to Un\G27903)
The start number and the number of points of RWr for each station are stored.
Address
Un\G26880 to Un\G26881
Un\G26882 to Un\G26883
Un\G26884 to Un\G26885
Un\G26886 to Un\G26887
Un\G27360 to Un\G27361
Un\G27362 to Un\G27363
Un\G27364 to Un\G27903
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 26880 + (station No.)  4
• Size buffer memory address = 26882 + (station No.)  4
APPX
192
Appendix 3 Buffer Memory
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.120 offset
Station No.120 size (in units of words)
System area
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.120 offset
Station No.120 size (in units of words)
System area