Wiring products
The following describes the devices used for CC-Link IE TSN.
■Ethernet cable
Use Ethernet cable that meets the following standards.
Communication
Ethernet cable
speed
1Gbps
Category 5e or higher, straight cable (double shielded, STP)
Cables for CC-Link IE TSN are available from Mitsubishi Electric System & Service Co., Ltd. (Catalogs for cable are also
available.)
In addition, the connector processing of cable length is available for your preference. Please consult your local Mitsubishi
representative.
Communication
Type
speed
1Gbps
Category 5e or higher, straight cable (double shielded, STP)
A communication error may occur due to high-frequency noise from devices other than a programmable
controller in a given connection environment. The following describes countermeasures to be taken on the
FX5-CCLGN-MS side to avoid high-frequency noise influence.
Wiring
• Use a duplex shield type cable.
• Do not bundle the cable with the main circuit or power cable or do not place it near those lines.
• Place the cable in a duct.
■Switching hub
Use the following industrial switching hubs.
Term
TSN switching hub
General-purpose
switching hub
A switching hub can be used for cascade connection.
When the switching hub is used for cascade connection, check the specifications of the switching hub used.
Precautions
• Since there are different restrictions for system configuration using a TSN switching hub and system configuration using a
general-purpose switching hub, setting with an engineering tool is required. ( Page 64 SYSTEM CONFIGURATION)
• Do not configure a ring topology when modules are connected to a switching hub. Doing so, all stations will fail and data
links cannot be performed.
6 WIRING
88
6.2 CC-Link IE TSN Wiring
Description
For the models and usage methods of the switching hubs, refer to the CC-Link Partner Association
website (www.cc-link.org).
Connector
Type
RJ45
The following conditioning cables:
connector
• IEEE 802.3 (1000BASE-T)
• ANSI/TIA/EIA-568-B (Category 5e)
Model (Manufacturer)
SC-E5EW series (Mitsubishi Electric System & Service Co., Ltd.)
Authentication Class
Authentication Class B
device
Authentication Class A