Refresh settings

Assign link refresh ranges between the following devices.
• SB, SW, link devices (RX, RY, RWr, RWw) of the FX5-CCLGN-MS  Devices of the FX5 CPU module
Setting method
The procedure for the refresh settings is as follows.
1.
Set the required items.
2.
Click the [Apply] button to finish "Refresh Settings".
Setting items
The setting items for the refresh settings are as follows.
Item
Description
Device Assignment
Right-click in the setting window and select a link device assignment method
Method
from the "Device Assignment Method" menu.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start: Enter the numbers of points and start numbers of link devices.
Link Side
Set the link refresh ranges of SB and SW. One link refresh range can be set
for each of SB and SW. ( Page 32 Link refresh)
Ex.
00000H
·
001FFH
00000H
·
001FFH
CPU Side
Device name
(SB)
Device name
(SW)
FX5-CCLGN-MS
Setting range
For master stations For local stations
• Start/End
• Points/Start
(Default: Start/End)
■Device Name
• SB (fixed)
• SW (fixed)
■Points
• SB: 16 to 4096 (set in increments of 16 points)
• SW: 1 to 4096
(Default: empty)
■Start
• SB: 0H to FF0H (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
00000H
(Default: empty)
Device name
·
■End
(SB)
001FFH
• SB: FH to FFFH (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
00000H
Device name
(Default: empty)
·
(SW)
001FFH
■Target
• Specify Device
(Default: empty)
■Device name
• Specify Device (link side is SB): SB, M, L, B, D,
R
• Specify Device (link side is SW): SW, M, L, B, D,
FX5 CPU module
R
(Default: empty)
■Points, End
Displayed according to setting of "Start".
(Default: empty)
■Start
Device range of FX5 CPU modules (Set bit
devices in increments of 16 points and word
devices in increments of 4 points.)
(Default: empty)
7 PARAMETER SETTINGS
7.3 Basic Settings
7