Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 147

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Function
Function
type
Operation test/
Communication Test
execution
function
Remote Operation
*1 If the setting on the "Specify Connection Destination Connection" window of the engineering tool is as follows, remote operation cannot
be executed with "All Stations Specified".
Connection via Ethernet with the selections "Ethernet Board" for the personal computer-side I/F and "CC IE TSN/Field Module" for the
programmable controller-side I/F
When starting the CC-Link IE TSN/CC-Link IE Field diagnostics by specifying "Other Station (Single Network)"
or "Other Station (Co-existence Network)" in "Other Station Setting" on the "Specify Connection Destination
Connection" window, the following restrictions apply.
• A communication test cannot be used.
• If MELSECNET/H, multidrop connection of serial communication modules, an interface board for a personal
computer, or network modules of the MELSEC-Q/L series are included in the communication path,
diagnostics cannot start.
Description
• This test specifies the network number and
station number or the IP address to check
whether transient transmission can be
performed from the connected station (own
station) to the communication destination.
• Transient transmission to the specified
communication destination can be
checked. In addition, when the
communication destination is a station on
another network, this test can check the
relay stations that are passed through until
transient transmission arrives from the
connected station (own station) at the
communication destination.
This function can remotely operate (RUN,
STOP, and RESET) the FX5 CPU module
and slave module.
Connection destination of
engineering tool
Master
Local station
station
*1
*1
10 TROUBLESHOOTING
10.3 Checking the Network Status
Reference
Page 152
Communication test
10
Page 153 Remote
operation
145