IP address verification
result
Detected slave stations are not in
the saved CC-Link IE TSN
structure.
Precautions
In the CC-Link IE TSN structure, when a station number is set to a slave station and parameters are written to the FX5 CPU
module, the station number of the slave station is held in the master station. When parameters are not to be written in FX5
CPU modules, they are saved in the CC-Link IE TSN structure as slave stations with the station number not set.
Register the profile of the target device to detect in advance.
If the profile is not registered, the following may be displayed.
• "Model Name" is "General Remote Station", "General Local Station", or "General Extension Module".
• "Station Type" is "Remote Station", "Local Station", or "Extension Module".
For how to register a profile, refer to the following.
 GX Works3 Operating Manual
• Even when the profile is registered, if modules that are not available for detection of connected/
disconnected devices are used, "Model Name" and "Station Type" are not displayed correctly.
• This function is not available for local stations.
• Reserved stations or data link faulty stations cannot be detected by this function.
• If this function is executed when the slave station has been disconnected after the master station was
powered on, the setting of "Reserved Station/Error Invalid Station" does not change to "Reserved Station",
but it becomes "No Setting".
• A module that cannot be used with FX5-CCLGN-MS, for example, a module with a safety communication
function or a module that requires a CANopen profile, may be detected.
Operation
Display
Connect
Detected slave stations are added. (Settings other than "IP Address",
"STA#", and "Station Type" are default)
When adding a device, the defaults other than IP address, station
number, and station type are set.
(However, if the station number of the detected device has not been set,
the station number is also set to the default.)
Added slave stations are displayed in the list of stations in the following
order.
• Modules other than extension modules: In the order of IP addresses,
following disconnected slave stations.
• Extension modules: In the order of sub-IDs, following connected main
modules and extension modules.
When station numbers of
detected slave stations
are not set
A station number is
automatically numbered as the
lowest unused station number in
the range from 1 to 120.
The order of automatic
numbering is the same as the
displayed order in the list of
stations (see left).
7 PARAMETER SETTINGS
7.5 "CC-Link IE TSN Configuration" Window
7
103