Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 163

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
1805H
• The total cyclic data size of all slave
stations on the authentication Class A
device side at the boundary between
authentication Class B and
authentication Class A exceeds 2K
bytes.
• The total cyclic data size of all slave
stations on the authentication Class A
device side at the boundary between
authentication Class B and
authentication Class A exceeds 2K
bytes.
1811H
A stop error has been detected in the CPU
module.
1830H
Number of reception requests of transient
transmission (link dedicated instruction)
exceeded the upper limit of simultaneously
processable requests.
1845H
Too much processing of transient
transmission (link dedicated instruction)
and cannot perform transient transmission.
1D01H
System error
1D10H
System error
to
1D11H
1D20H
System error
20E0H
The module cannot communicate with the
CPU module.
2160H
IP address duplication was detected.
2220H
The parameter setting is corrupted.
2221H
• The set value is out of the range. Or the
setting values of the master station and
local stations are not consistent.
• Parameters that are not supported by
the firmware version of the network
module have been set.
24C0H
System error
to
24C3H
24C6H
System error
2600H
System error
2610H
System error
3000H
System error
3009H
The result when the value set in
"Communication Period Interval Setting" in
"Communication Period Setting" under
"Basic Settings" of the master station is
multiplied by "Communication Period
Setting" of the slave station set in "Network
Configuration Settings" under "Basic
Settings" is out of the range.
Action
Check the connection and setting on the end side of the station shown in
detailed information 2 based on the error definition and cause and take the
following actions.
• Do not set the total cyclic data size of all slave stations on the
authentication Class A device side at the boundary between
authentication Class B and authentication Class A to exceed 2K bytes.
• Do not set the total cyclic data size of all slave stations on the side of the
station with a communication speed of 100Mbps at the boundary between
the station with a communication speed of 1Gbps and the station with a
communication speed of 100Mbps to exceed 2K bytes.
Check the error of the CPU module in "Module Diagnostics" of the
engineering tool and take action.
Lower the transient transmission usage frequency, and retry the operation.
Correct the transient transmission (link dedicated instruction) execution
count.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
The hardware failure of the CPU module may have been occurred. Please
consult your local Mitsubishi representative.
Check the IP addresses.
Check the detailed information of the error in "Module Diagnostics" of the
engineering tool, and write the displayed parameter. If the same error occurs
again, the possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Check the detailed information of the error in "Module Diagnostics" of the
engineering tool, and correct the parameter setting corresponding to the
parameter number.
• Check the firmware version of the network module. If parameters that are
not supported are set, update the firmware version or correct the
parameters.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Check the detailed information in "Module Diagnostics" of the engineering
tool. Correct the parameter settings described below so that the result when
the value set in "Communication Period Interval Setting" in "Communication
Period Setting" under "Basic Settings" of the master station is multiplied by
"Communication Period Setting" of the slave station set in "Network
Configuration Settings" under "Basic Settings" becomes within 16ms.
• "Communication Period Interval Setting" in "Basic Settings"
• "Communication Period Setting" of the relevant slave station in "Network
Configuration Settings"
Set a value to "Communication Period Setting" of slave stations by selecting
a multiple value on "Multiple Period Setting" of "Communication Period
Setting" under "Basic Settings".
Detailed
information 1
Detailed
information 2
■Own station
information
• Intelligent module
No.
• Network No.
• Station No.
• IP address
■Target station
information
• Network No.
• Station No.
• IP address
■Parameter
information
• Parameter type
■
■Parameter
information
• Parameter type
• Intelligent module
No.
• Parameter No.
• Network No.
• Station No.
■
■
■Target station
information
• Station Number
• IP address
10 TROUBLESHOOTING
161
10.5 List of Error Codes