Event List - Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

10.7

Event List

This section lists the events which occur in CC-Link IE TSN.
The event history is displayed when the [Event History] button in the [Error Information] tab in the "Module Diagnostics"
window of the FX5-CCLGN-MS is clicked. ( Page 141 Error Information)
System
Event
Description
code
00800
Link-down
00907
Divided messages receive timeout error
00C40
Slave station parameter automatic setting:
Interruption
00C41
Slave station parameter automatic setting: Parameter
update interruption
00C42
Slave station parameter automatic setting: System
error
00C43
Slave station parameter automatic setting:
Transmission timeout
00C44
Slave station parameter automatic setting: Receive
timeout
00C46
Slave station parameter automatic setting: SLMP
transmission error
00C47
Slave station parameter automatic setting: CPU
module access failure
00C48
Slave station parameter automatic setting: No target
station parameter
10 TROUBLESHOOTING
180
10.7 Event List
Cause
The system was linked down by removing a device (such as an external device).
• Sufficient data for the data length could not be received.
• The remaining part of the divided message could not be received.
An abnormal response was received from the slave station, and slave station parameter
automatic setting processing was interrupted. (For details on slave station response
codes, refer to the manual for the slave station.)
An abnormal response was received from the slave station, and parameter update
processing of slave station parameter automatic setting was interrupted. (For details on
slave station response codes, refer to the manual for the slave station.)
An error occurred while the slave station parameter automatic setting was executing.
Transmission timed out while communicating with the slave station parameter automatic
setting.
The specified period of time expired without receiving while communicating with the
slave station parameter automatic setting.
An error occurred while transmitting SLMP for the slave station parameter automatic
setting.
Access to the CPU module failed during slave station parameter automatic setting.
The station parameter file targeted during slave station parameter automatic setting was
not stored in the CPU module.