Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 177

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
D61DH
Parameter error (device overlap error
(RY))
D61EH
Parameter error (device overlap error
(RX))
D61FH
System error
D621H
Parameter error
D622H
Parameter error (error in the total number
of slave stations)
D625H
Parameter error (station-based block data
assurance setting error)
D628H
Parameter error (station type error)
D629H
Parameter error (station number range
error)
D62AH
Parameter error (data link faulty station
setting error)
D62BH
Parameter error (output setting error
during CPU STOP)
D630H
System error
D637H
The UINI instruction was executed at a
station where the station number/IP
address has been already set by
parameter.
D639H
After setting a station number/IP address
with the UINI instruction, the instruction
was executed again.
D641H
Parameter error (IP address error)
D642H
Parameter error (gateway address setting)
D643H
Parameter error (communication cycle
setting)
Action
• Write the network parameter to the CPU module again.
• Execute again after correcting the offset or size of the slave station link
device in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the offset or size of the slave station link
device in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Please consult your local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the total number of slave stations.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the station-based block data assurance
setting.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the station type in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the station number in the setting data so it
is within 1 to 120.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the data link faulty station setting.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the output settings during CPU STOP.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Execute again after setting "Station No./IP Address Setting Method" under
"Station No./IP Address Setting" in "Required Settings" to "Program".
Station number/IP address setting with the UINI instruction is limited to one
time only. Reset the CPU module, and retry the operation.
• Write the network parameter to the CPU module again.
• Execute again after correcting the IP address in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the gateway address setting in the setting
data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute again after correcting the communication cycle setting in the
setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Detailed
information 1
Detailed
information 2
10 TROUBLESHOOTING
175
10.5 List of Error Codes