Step 6 You can perform the following operations after clicking the device icon:
----End

8.4.2.2.3 Setting the Transparent Transmission Function for the ECC800 Collector

Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > NMS Application > Transparent Transmission Channel.
Step 3 Set COM2 (Port:3212) to Enable and click Submit.
Step 4 Log in to the NetEco WebUI as an administrator.
Step 5 Choose Configuration > Configuration Management > Data Center Planning. The Data
Center Planning window is displayed.
Step 6 Select the management domain to add a device. The management domain can be a modular,
rack, or equipment room.
Step 7 (Optional) If the management domain is a rack, click the management domain and choose
Design under
Step 8 In the lower-left corner of the page, click the Device tab.
Step 9 Click the drop-down list box in Type and select Sensor.
Step 10 In this example, a Polymer temperature and humidity (T/H) sensor is added in the equipment
room of the root node. Select the device to be added and drag its icon to the management
domain.
Step 11 Click the device. In the device parameter area on the right, set device parameters according to
the following table.
Issue 02 (2019-12-20)
Select Manage under
Using the transparent transmission function, the NMS can directly manage southbound
components that are not monitored by the ECC800.
In this example, the COM2 port of the ECC800 is used for transparent transmission.
Mapping relationship: COM1 corresponds to port 3211, COM2 port 3212, COM3 port 3213, and COM4
port 3214.
If the port is set for the first time, you are prompted to set an authentication password.
On the Set Authentication Password tab page, set Authentication password and
Confirm authentication password and click Submit.
Enable Security Authentication is set to Enable by default. If so, an authentication password must be
set. If Enable Security Authentication is set to Disable, there is no need to set an authentication
password but this is risky.
If the port has been used, you will be prompted that the transparent transmission function
cannot be enabled and you need to select an idle port.
. The page for adding a device is displayed. Otherwise, skip this step.