Huawei FusionModule1000A Commissioning Manual page 58

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
2.
Wait for one minute and turn the Enable Control key rightward. After the LCD changes from EEE to
Ad, press Reseton the extinguishant control panel to reset the extinguishant control panel.
Issue 02 (2019-12-20)
Figure 7-23 Pressure switch
The extinguishant control panel generates a LOCAL FIRE alarm, and Extinguishant Release
indicator turns on. The warning sign is steady on.
LOCAL FIRE terminal generates a LOCAL FIRE alarm signal.
Figure 7-24 Extinguishant Released indicator on
Reset the extinguishant control panel.
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning
51