FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
----End
Follow-up Procedure
?.2.Changing the Preset Password for the VCN Servers
Context
To ensure password safety, you need to change the OMU Portal login password periodically.
Procedure
Step 1 Log in to the OMU portal of the MPU server as the Admin user.
Step 2 Click Change Password at the upper right corner, as shown in
Figure 8-25 Changing a password
Step 3 Enter Old Password, New Password, and Confirm Password and click Save.
Figure 8-26 Changing a password 02
----End
Issue 02 (2019-12-20)
The VCN automatically restarts after the IP address is modified. The restart takes about 5
minutes. After the restart, use the new IP address to access the VCN.
Change the PC IP address to an address in the network segment of the new VCN IP
address, enter the VCN IP address in the address box of the Internet browser, and log in
to the OMU Portal system.
(Optional) Deploying IVS in Stack Mode. For details, log in to the
https://e.huawei.com/, search for the VCN510&VCN520&VCN540 Product
Documentation, open the documentation, and see the section Deploying IVS in Stack
Mode.
(Optional) Deploying MPUs in Cluster Mode. For details, log in to the
https://e.huawei.com/, search for the VCN510&VCN520&VCN540 Product
Documentation, open the documentation, and see the section Deploying MPUs in
Cluster Mode.
Copyright © Huawei Technologies Co., Ltd.
8 Commissioning Core Components
Figure
8-25.
100