Huawei FusionModule1000A Commissioning Manual page 51

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Step 11 Press RESET to reset the fire alarm control panel.
Step 12 (Optional) Check whether the fire alarm signals are reported to the management system.
Step 13 Reconnect cables to the electromagnetic valve.
Issue 02 (2019-12-20)
Figure 7-12 Smoke detector installation reference line
Figure 7-13 Heat detector installation reference line
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning
44