FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
No.
Procedure
Step 1 Tap
page.
To change the settings, you need to log in as the Admin user. For the password, see the
management system initial configuration table.
Set the teamwork function on the teamwork setting screen. Parameters to be set for the master
device include Teamwork unit no., Teamwork unit address, Teamwork function,
Network, Total number of units, Number of running units, Standby mode rotation,
Rotation period, Rotation time, Forced rotation, Requirement control, and Cascade.
However, a slave device only supports parameters like Teamwork unit no., Teamwork unit
address, and Teamwork function.
Figure 8-7 Teamwork setting screen
Table 8-7 Teamwork settings
Parameter
Teamwork
group No.
Smart
Issue 02 (2019-12-20)
Parameters
Note
critical alarms,
as shown in
> Teamwork Settings on the main screen to enter the Teamwork Settings
Description
The number of the
teamwork controlled
group, which is the
same for all the devices
in the group.
Smart cooling product
Copyright © Huawei Technologies Co., Ltd.
8 Commissioning Core Components
.
Configuration
Principle
Set the assigned
teamwork control
number.
Set the assigned unit
Default Value
1
NA
67