Huawei FusionModule1000A Commissioning Manual page 33

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
System
Cooling system
Issue 02 (2019-12-20)
Check Item
Operation Method
Phase sequence
Verify that the L1, L2,
of indoor and
L3, N, and PE wires are
outdoor unit
connected for the indoor
cables
and outdoor units in the
correct phase sequence
using a phase sequence
meter.
Water refill for
Check whether the water
the smart
refill valve is open, and
cooling product
whether the water refill
humidifier
pressure meets the
requirement.
Outdoor unit air
Check the outdoor unit
intake and
air intake and exhaust
exhaust vents
vents.
Smart cooling
Check the smart cooling
product
product compressor.
compressor
pads
Liquid level
Check the liquid level
detector
detector fastener.
fastener
Smart cooling
Check the connection of
product
smart cooling product
teamwork and
teamwork and signal
signal cables
cables.
Smart cooling
Check the pipe
product pipe
connections for the
connection
air-cooled precision
Copyright © Huawei Technologies Co., Ltd.
cell voltage using a
multimeter.
Measure the battery
string voltage using a
multimeter.
5 Check Before Power-On
Reference
the design
requirements and
installed securely.
Battery electrodes are
correctly connected.
The voltage is within
the rated voltage
range of batteries.
The battery string
voltage equals the
single battery voltage
multiplied by the
number of batteries.
The voltage
measurement result
meets the requirement
of system power
backup.
The phase sequence is
correct.
The water refill valve is
open, and the water refill
pressure is 0.1–0.7 MPa.
Outdoor unit air intake
and exhaust vents are not
blocked.
All smart cooling product
compressor pads are
removed.
The liquid level detector
fastener has been
removed.
Cables are securely
connected and meet the
design requirements.
The refrigerant
circulation pipeline,
humidifier water refill
pipeline, and condensate
26