Figure 8-33 Positions of power switches
If the power indicator is on and other indicators are off, the power-on process succeeds. If a
yellow fault indicator is on, rectify the fault before continuing follow-up operations.
Step 3 Unlock the keypad.
The keypad is locked to prevent misoperation.
Step 4 Set the time displayed on the fire alarm control panel.
Open the control panel and adjust the time from the rear of the display panel.
There are three buttons and one light emitting diode on the rear of the panel. The three buttons
are S12, S11, and S10, respectively indicating switchover, adding one to the first two values,
and add one for the last two values of the nixie tube.
Issue 02 (2019-12-20)
To unlock the keypad, press KEY ON/OFF and QUERY TIME in turn.
To lock the keypad, press KEY ON/OFF when the keypad is unlocked.
The keypad will be locked if no operation is performed in 4 minutes.