Procedure
Enabling function
1. Select the "Syslog Client" check box.
2. Click the "Set Values" button.
Creating a new entry
1. In the "Syslog Server Address" input box, enter the IP address of the Syslog server on which
the log entries will be saved.
2. Click the "Create" button. A new row is inserted in the table.
3. In the "Server Port" input box, enter the number of the UDP port of the server.
4. Click the "Set Values" button.
Note
The default setting of the server port is 514.
Changing the entry
1. Delete the entry.
2. Create a new entry.
Deleting an entry
1. Select the check box in the row to be deleted.
2. Click the "Delete" button. All selected entries are deleted and the display is refreshed.
4.5.12

Fault Monitoring

4.5.12.1

Link Change

Configuration of fault monitoring of status changes on connections
On this page, you configure whether or not an error message is triggered if there is a status
change on a network connection.
If connection monitoring is enabled, an error is signaled
● when there should be a link on a port and this is missing.
● or when there should not be a link on a port and a link is detected.
A fault causes the fault LED on the device to light up and, depending on the configuration, can
trigger a trap, an e-mail, or an entry in the event log table.
SCALANCE S615 Web Based Management
Configuration Manual, 11/2019, C79000-G8976-C388-08