Siemens SIMATIC NET SCALANCE S615 Configuration Manual page 129

Industrial ethernet security web based management
Hide thumbs Also See for SIMATIC NET SCALANCE S615:
Table of Contents

Advertisement

You can download existing CLI configurations (RunningCLI) and upload your own CLI scripts
(Script).
Note
The downloadable CLI script is not intended to be uploaded again unchanged.
CLI commands for saving and loading files cannot be executed with the CLI script file (Script).
Exchange of configuration data with STEP 7 Basic/Professional using a file
You use the two file types "RunningSINEMAConfig" and "SINEMAConfig" to exchange
configuration data between a device (WBM) and STEP 7 Basic/Professional via a file.
Requirements:
● Same article number
● Same firmware version
● Password
You assign the password in the WBM under "System > Load&Save > Passwords".
You can use the file types as follows:
● For offline diagnostics
You can save the faulty configuration of a device as "RunningSINEMAConfig" via the WBM
and import it in STEP 7 Basic/Professional. No connection to a real device is required for the
diagnostics in STEP 7 Basic/Professional. You can export a corrected configuration and
load it as "SINEMAConfig" again using the WBM.
● For configuration
No connection to a real device is required to configure a device in STEP 7 Basic/
Professional. You can export the configuration and load it as "SINEMAConfig" to the real
device using the WBM.
X509 certificates
The following file types can be loaded into the device:
● .crt, pem, zip: Maximum file name length 255 characters
● .p12: Maximum file name length 248 characters
SCALANCE S615 Web Based Management
Configuration Manual, 11/2019, C79000-G8976-C388-08
Configuring with Web Based Management
4.5 "System" menu
129