"Optional Settings" area
● Auto Firewall/NAT Rules
– Enabled
– Disabled
● Type of connection
Specify the type of VPN connection. For more detailed information, refer to the section "VPN
connection establishment".
– Auto
– Permanent
– Wake-up SMS (only with M87x)
– Digital In
– Digital In & Wake-up SMS (only with M87x)
● Use Proxy
Specify whether a connection to the defined SINEMA RC Server is established via a proxy
server. Only the proxy servers can be selected that you configured in "System > Proxy
Server".
SCALANCE S615 Web Based Management
Configuration Manual, 11/2019, C79000-G8976-C388-08
The firewall and NAT rules are created automatically for the VPN connection. The
connections between the configured exported subnets and the subnets that can be
reached via the SINEMA RC Server are allowed. The NAT settings are implemented as
configured in the SINEMA RC Server.
You can enable SINEMA RC to access specific services of the device under "Security >
Firewall > Predefined IPv4".
You will need to create the firewall and NAT rules yourself.
The device adopts the settings of the SINEMA RC Server. You configure the settings on
the SINEMA RC Server in "Remote connections > Devices". You will find further
information on this topic in the operating instructions "SINEMA RC Server".
The settings of the SINEMA RC Server are ignored. The device establishes a VPN
connection to the SINEMA RC Server. The VPN tunnel is established permanently
The settings of the SINEMA RC Server are ignored. When the device receives a
command SMS message (wake-up SMS message), it attempts to establish a connection
to the SINEMA RC Server. On condition that in "System > SMS > SMS Command" it is
specified who a command SMS of the class "System" will be accepted from.
The settings of the SINEMA RC Server are ignored. If the "Digital In" event occurs, the
device attempts to establish a VPN connection to the SINEMA RC Server. This is on
condition that the event "Digital In" is forwarded to the VPN connection. To do this in
"System > Events> Configuration" activate "VPN Tunnel" for the "Digital In" event.
The settings of the SINEMA RC Server are ignored. If the "Digital In" event occurs or
when the device receives an SMS command, it attempts to establish a VPN connection
to the SINEMA RC Server.
Configuring with Web Based Management