Monitoring Of The Connection - Siemens SIMATIC NET SCALANCE S615 Configuration Manual

Industrial ethernet security web based management
Hide thumbs Also See for SIMATIC NET SCALANCE S615:
Table of Contents

Advertisement

● Size [KB]
The first row "Available memory" shows how much memory is available for backups on the
device. When you create a backup, the available memory space is reduced accordingly.
The other rows show the size of each backup.
● Restore
Click the "Restore" button to load the relevant backup on the device.
Procedure
1. Enter the required name.
2. Click the "Create" button.
The current configuration is saved as a configuration backup.
Saving the backup may take some time. A new row is created for the backup. The size of the
backup is displayed and subtracted from the available memory space.
4.5.22

Monitoring of the connection

On this page, you activate a ping test that monitors connections. During the ping test, the device
sends ICMP echo request packets (pings) to the configured destination address at regular
intervals. If this destination address does not respond, the device tries to reach the destination
address again. If all ping attempts (retries) are unsuccessful, the ping test is considered to have
failed or the group is considered unreachable. If the group is not reachable, the device initiates
the configured action on the selected interface. If all 5 actions have been executed or after a
restart, the device starts again with the first action.
Description
● Enable Connection Check
Enable or disable the ping test for connection monitoring.
SCALANCE S615 Web Based Management
Configuration Manual, 11/2019, C79000-G8976-C388-08
Configuring with Web Based Management
4.5 "System" menu
207