Description
The table has the following rows:
● Status
Shows the status of the PLUG. The following are possible:
– ACCEPTED
– NOT ACCEPTED
– NOT PRESENT
– FACTORY
– MISSING
● Device Group
Shows the SIMATIC NET product line that used the C-PLUG or KEY-PLUG previously.
● Device Type
Shows the device type within the product line that used the C-PLUG or KEY-PLUG
previously.
● Configuration Revision
The version of the configuration structure. This information relates to the configuration
options supported by the device and has nothing to do with the concrete hardware
configuration. This revision information does not therefore change if you add or remove
additional components (modules or extenders), it can, however, change if you update the
firmware.
● File System
Displays the type of file system on the PLUG.
● File System Size
Displays the maximum storage capacity of the file system on the PLUG.
● File System Usage
Displays the memory utilization of the file system of the PLUG.
● Firmware on PLUG (as of firmware version 4.3)
When enabled, the firmware will be stored on the PLUG. This means that automatic
firmware updates/downgrades can be made with the PLUG.
SCALANCE S615 Web Based Management
Configuration Manual, 11/2019, C79000-G8976-C388-08
There is a PLUG with a valid and suitable configuration in the device.
Invalid or incompatible configuration on the inserted PLUG.
There is no C-PLUG or KEY-PLUG inserted in the device.
PLUG is inserted and does not contain a configuration. This status is also displayed
when the PLUG was formatted during operation.
There is no PLUG inserted. Functions are configured on the device for which a license
is required.
Configuring with Web Based Management
4.5 "System" menu
181