MODE-H: APPLICATION SPECIFIC FUNCTIONS
No.
Parameter
GROUP-1: MULTI-PUMP FUNCTION PARAMETERS
H101 No Of Pump
Selection
H102 Pump Start Hold
Time
H103 Pump Stop Hold
Time
H104 Pump Continuous
ON Time Limit
H105 Pump Changeover
Time
6
Amtech
6-34
Unit
Def
Min
Max
0
0
4
Sec
60.0
0.1
3600.0
Sec
60.0
0.1
3600.0
Hrs
8
2
168
Sec
3
1
120
Res
Description
1
Select number of pumps to be controlled.
0.1
If the PID output reaches to upper limit and
remains there for more than the set time, the
next pump will be switched ON.
0.1
If the PID output reaches to lower limit and
remains there for more than the set time, the
next pump will be switched OFF.
1
If pump's ON/OFF control is not carried out for
more than the set time, the pump will change to
the longest operating pump to the shortest
operating pump.
1
Set the time for changing from the pump that
has been operating longest to the pump
operating shortest.
WP