No. Parameter
D305 DC Brake Time
GROUP-4: LIMITING PARAMETER
D401 Stall Current Limit
D402 Adjustable Over
Current Level
D403 Acceleration
Current Limit
D404 Under Current
Level
Axpert-Eazy AC Variable Frequency Drive
Unit
Def
Min
Max
Sec
0.0
0.0
25.0
%
125.0
0.0
200.0
%
300
50
300
%
150
50
200
%
0
0
90
Res
Description
0.1
It is amount of time that DC braking will be
applied when stop command is issued. To
disable DC Braking operation set this parameter
to zero.
0.1
Set the current value as a percentage of motor
rated current for normal running condition.
The default value is 155%, when heavy duty is
set.
1
Set the upper current limit as a percentage of
motor rated current for running condition. When
set to 300%, this feature is disabled.
1
Set the upper current limit as a percentage of
motor rated current for Acceleration.
1
Set the lower current limit as a percentage of
motor rated current for running condition.
WP
6
6-25